M-Series MZ-GE Engineering Manual

M-Series - MSZ/MUZ-GENA2 Heat Pump Systems (August 2014)
MSZ-GENA2-29
© 2014 Mitsubishi Electric US, Inc.
Due to continuing improvement, above specication may be subject to change without notice.
3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE
(1) Cooling Capacity
Model
Indoor
air
Outdoor intake air DB temperature (˚F)
IWB
(˚F)
75 85 95 105 115
TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC
MUZ-GE09NA2
71 11.0 7.6 0.59 10.3 7.1 0.64 9.7 6.6 0.69 9.0 6.2 0.73 8.3 5.7 0.76
67 10.4 8.6 0.55 9.7 8.0 0.61 9.0 7.4 0.66 8.4 6.9 0.70 7.7 6.3 0.73
63 9.8 9.4 0.53 9.1 8.7 0.58 8.5 8.1 0.63 7.7 7.3 0.67 7.0 6.7 0.70
MUZ-GE12NA2
71 14.7 8.9 0.85 13.7 8.3 0.94 12.9 7.8 1.01 12.0 7.3 1.06 11.0 6.7 1.10
67 13.9 10.3 0.81 13.0 9.6 0.89 12.0 8.9 0.96 11.2 8.3 1.02 10.3 7.6 1.07
63 13.1 11.4 0.77 12.1 10.6 0.85 11.3 9.9 0.92 10.3 9.0 0.98 9.4 8.2 1.02
MUZ-GE15NA2
71 17.2 11.4 0.96 16.0 10.7 1.05 15.1 10.0 1.13 14.0 9.3 1.19 12.9 8.6 1.24
67 16.2 13.0 0.91 15.1 12.1 1.00 14.0 11.2 1.08 13.0 10.4 1.14 12.0 9.6 1.20
63 15.3 14.2 0.86 14.1 13.2 0.96 13.2 12.3 1.03 12.0 11.2 1.10 10.9 10.2 1.14
MUZ-GE18NA-1
71 21.1 12.2 1.46 19.7 11.4 1.60 18.5 10.7 1.72 17.2 9.9 1.81 15.8 9.1 1.89
67 20.0 14.2 1.38 18.6 13.2 1.52 17.2 12.2 1.64 16.0 11.4 1.74 14.7 10.4 1.82
63 18.7 15.8 1.31 17.4 14.7 1.45 16.2 13.6 1.57 14.7 12.4 1.67 13.4 11.3 1.74
MUZ-GE24NA
71 27.6 17.0 1.60 25.8 15.9 1.76 24.2 14.9 1.89 22.5 13.9 1.99 20.7 12.8 2.07
67 26.1 19.6 1.51 24.3 18.2 1.67 22.5 16.9 1.80 20.9 15.7 1.91 19.2 14.4 2.00
63 24.5 21.7 1.44 22.7 20.1 1.59 21.2 18.7 1.72 19.2 17.0 1.84 17.6 15.5 1.91
NOTE
: 1. IWB: Intake air wet-bulb temperature
TC: Total Capacity (×10
3
Btu/h)
SHC: Sensible Heat Capacity (×10
3
Btu/h)
TPC: Total Power Consumption (kW)
2. SHC is based on 80˚F of indoor Intake air DB temperature.