M-Series MUZ-GE Technical & Service Manual

8
Outdoor unit model MUZ-GE24NA MUY-GE24NA
Capacity
Rated (Minimum~Maximum)
Cooling 1 Btu/h
22,500
(8,200 ~ 31,400)
22,500
(8,200 ~ 31,400)
Heating 47
1 Btu/h
27,600
(7,500 ~ 36,900)
Capacity
Rated (Maximum)
Heating 17 2 Btu/h 16,000 (24,600)
Power consumption
Rated (Minimum~Maximum)
Cooling 1W
1,800 (570
~ 3,580)
1,800 (570
~ 3,580)
Heating 47
1W
2,340 (520
~ 3,650)
Power consumption
Rated (Maximum)
Heating 17 2 W 1,770 (3,290)
EER
1
[SEER]
3 Cooling 12.5 [19.0]
HSPF IV
4 Heating 10.0
COP Heating
1 3.46
Power supply V , phase , Hz 208/230 , 1 , 60
Max. fuse size (time delay) A 20
Min. circuit ampacity A 17.1
Fan motor F.L.A 0.93
Compressor
Model SNB172FQKMT
R.L.A 12.9
L.R.A 16.1
Refrigeration oil
(Model)
L 0.40 (FV50S)
Refrigerant control Linear expansion valve
Sound level
1
Cooling dB(A) 55
Heating dB(A) 55
Defrost method Reverse cycle
Dimensions
W in. 33-1/16
D in. 13
H in. 34-5/8
Weight Ib. 119
External nish Munsell 3Y 7.8/1.1
Remote controller Wireless type
Control voltage
(by built-in transformer)
VDC 12-24
Refrigerant piping Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in. 3/8 (0.0315)
Gas in. 5/8 (0.0315)
Connection method
Indoor Flared
Outdoor Flared
Between the indoor &
outdoor units
Height difference ft. 50
Piping length ft. 100
Refrigerant charge (R410A) 4 lb. 3 oz.
NOTE: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB)
(Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB
2: (Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
OBH549G