M-Series MSZ-GE Engineering Manual
Table Of Contents
- Contents
- 1. INDOOR UNITS
- 2. OUTDOOR UNITS
- 3. SYSTEM
- 3-1. SPECIFICATIONS
- 3-2. EXTERNAL DIMENSIONS
- 3-3. CENTER OF GRAVITY
- 3-4. ELECTRICAL WIRING DIAGRAMS
- 3-5. REFRIGERANT SYSTEM DIAGRAMS
- 3-6. CAPACITY CORRECTION CURVE BY TEMPERATURE
- 3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE
- 3-8. CAPACITY CORRECTION CURVE BY REFRIGERANT PIPING LENGTH
- 3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH
- 3-10. CHARGE CALCULATIONS
- 3-11. AIR FLOW DATA
- 3-12. SOUND PRESSURE LEVELS
- 3-13. STANDARD OPERATION RANGE
- 3-14. MAXIMUM HEATING CAPACITY IN LOW AMBIENT TEMPERATURE
- 3-15. ACCESSORIES
M-Series - MSZ/MUZ-GE-NA Heat Pump Systems (August 2014)
MSZ-GE-NA-7
© 2014 Mitsubishi Electric US, Inc.
Due to continuing improvement, above specication may be subject to change without notice.
3-1. SPECIFICATIONS
Model name
MSZ-GE24NA
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay)/ Disconnect switch
A 20
Min. circuit ampacity A 1.0
Blower Motor (ECM) F.L.A 0.76
Airow
Powerful - High - Med - Low
COOL Dry
(Wet)
CFM
738-628-469-388
(661-562-420-347)
HEAT Dry
CFM 406-321-237-170-145
Moisture removal pt./h 5.1
Sensible Heat Factor 0.75
Sound level
Powerful - High - Med - Low
Cooling dB(A) 53-49-41-34
Heating
dB(A) 52-49-41-32
Cond. drain connection O.D. in. 5/8
Dimensions
W
in.
43-5/16
D 9-3/8
H 12-13/16
Weight Ib. 37
External nish Munsell 1.0Y 9.2/0.2
Control voltage (by built-in transformer) 12 - 24 VDC
NOTE: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) Rated frequency
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB Rated frequency
2: (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB Maximum frequency
MSZ-GE24NA