M-Series MSZ-GE Engineering Manual
Table Of Contents
- Contents
- 1. INDOOR UNITS
- 2. OUTDOOR UNITS
- 3. SYSTEM
- 3-1. SPECIFICATIONS
- 3-2. EXTERNAL DIMENSIONS
- 3-3. CENTER OF GRAVITY
- 3-4. ELECTRICAL WIRING DIAGRAMS
- 3-5. REFRIGERANT SYSTEM DIAGRAMS
- 3-6. CAPACITY CORRECTION CURVE BY TEMPERATURE
- 3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE
- 3-8. CAPACITY CORRECTION CURVE BY REFRIGERANT PIPING LENGTH
- 3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH
- 3-10. CHARGE CALCULATIONS
- 3-11. AIR FLOW DATA
- 3-12. SOUND PRESSURE LEVELS
- 3-13. STANDARD OPERATION RANGE
- 3-14. MAXIMUM HEATING CAPACITY IN LOW AMBIENT TEMPERATURE
- 3-15. ACCESSORIES
M-Series - MSZ/MUZ-GE-NA Heat Pump Systems (August 2014)
MSZ-GE-NA-43
© 2014 Mitsubishi Electric US, Inc.
Due to continuing improvement, above specication may be subject to change without notice.
3-12. SOUND PRESSURE LEVELS
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level
can be higher by about 2 dB than the displayed level during cooling and heating operation.
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
SPL(dB(A))
LINE
53
–
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
MSZ-GE24NA
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
SPL(dB(A))
LINE
43
–
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
MSY-GE09NA
SPL(dB(A)) LINE
49
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
MSY-GE15NA
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
SPL(dB(A))
LINE
45
–
53
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
MSY-GE12NA
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
COOLING(Rated)
HEATING(Rated)
NOTCH
COOLING(SHi)
HEATING(SHi)
NOTCH
COOLING(SHi)
HEATING(SHi)
NOTCH
COOLING(SHi)
HEATING(SHi)
NOTCH
MSZ-GE24NA
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level
can be higher by about 2 dB than the displayed level during cooling and heating operation.
WALL
UNIT
31-1/2 inch (0.8m)
39-3/8 inch (1m)
MICROPHONE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
SPL(dB(A))
LINE
53
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
MSZ-FE18NA
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
SPL(dB(A))
LINE
49
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
MSZ-D30NA
MSZ-D36NA
MSY-D30NA
MSY-D36NA
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
53
COOLING(Rated)
HEATING(Rated)
NOTCH
COOLING(Hi)
HEATING(Hi)
NOTCH
● NOTE:The sound level is measured in an anechoic
room where echoes are few,when compressor
stops.The sound may be bigger than displayed
level under actual installation condition by
surrounding echoes.The sound level can be higher
by about 2 dB than the displayed level during
cooling and heating operation.