MSZ-GE-NA-30
M-Series - MSZ/MUZ-GE-NA Heat Pump Systems (August 2014)
Due to continuing improvement, above specication may be subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
3-6. CAPACITY CORRECTION CURVE BY TEMPERATURE
MUZ-GE18NA-1
MUZ-GE24NA
71
67
63
2.0
1.9
1.8
1.7
1.6
1.5
1.4
1.3
Indoor intake air WB temperature (°F)
SHF at rating condition = 0.71
= 498 CFM
Airflow
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
Total power consumption
(kW)
71
67
63
65 75 85 95 105 115
1.3
1.4
1.5
1.6
1.7
1.8
1.9
2.0
2.1
2.2
Indoor intake air WB temperature (°F)
SHF at rating condition = 0.75
= 634 CFM
Airflow
Outdoor intake air DB temperature (°F)
Total power consumption
(kW)