10-3. TROUBLESHOOTING CHECK TABLE
No. Symptom LED indication
Abnormal point/
Condition
Condition Remedy
1
Outdoor unit
does not op-
erate.
1-time ash every
2.5 seconds
Outdoor power sys-
tem
Overcurrent protection cut-out operates 3 consecutive times
within 1 minute after the compressor gets started.
Reconnect connector of compres-
sor.
Refer to 10-5.
"How to check
inverter/compressor".
Check stop valve.
2
Outdoor thermistors Discharge temperature thermistor, n temperature thermistor,
defrost thermistor, P.C. board temperature thermistor, outdoor
heat exchanger temperature thermistor or ambient tempera-
ture thermistor shorts or opens during compressor running.
Refer to 10-5.
"Check of outdoor
thermistors".
3
Outdoor control sys-
tem
Nonvolatile memory data cannot be read properly.
(The left lamp of the OPERATION INDICATOR lamp on the
indoor unit lights up or ashes 7-time.)
Replace inverter P.C. board.
4
6-time ash
2.5 seconds OFF
Serial signal The communication fails between the indoor and outdoor unit
for 3 minutes.
Check connection between the in-
verter P.C. board and the relay P.C.
board. (FH15/18)
Refer to 10-5.
"How to check
miswiring and serial signal error.
5
11-time ash
2.5 seconds OFF
Stop valve/
Closed valve
Closed valve is detected by compressor current.
Check stop valve.
6
16-time ash
2.5 seconds OFF
4-way valve/
Pipe temperature
The 4-way valve does not work properly.
The indoor coil thermistor detects an abnormal temperature.
Refer to 10-5.
"Check of R.V.
coil".
Replace the inverter P.C. board.
7
17-time ash
2.5 seconds OFF
Outdoor refrigerant
system abnormality
A closed valve and air trapped in the refrigerant circuit are
detected based on the temperature sensed by the indoor and
outdoor thermistors and the current of the compressor.
Check for a gas leak in a
connecting piping etc.
Check the stop valve.
Refer to 10-5.
“Check of outdoor
refrigerant circuit”.
8
'Outdoor unit
stops and
restarts 3
minutes later'
is repeated.
2-time ash
2.5 seconds OFF
Overcurrent protec-
tion
Large current ows into the power module (IC700)
(FH06/09/12)/ IGBT module (IC700) (FH15/18).
Reconnect connector of compressor.
Refer to 10-5.
"How to check
inverter/compressor".
Check stop valve.
9
3-time ash
2.5 seconds OFF
Discharge tem-
perature overheat
protection
Temperature of discharge temperature thermistor exceeds
241°F (116°C), compressor stops. Compressor can restart if
discharge temperature thermistor reads 212°F (100°C) or less
3 minutes later.
Check refrigerant circuit and refrig-
erant amount.
Refer to 10-5.
"Check of LEV".
10
4-time ash
2.5 seconds OFF
Fin temperature
/P.C. board tem-
perature thermistor
overheat protection
Temperature of the n temperature thermistor on the heat sink
exceeds 167 - 187°F (75 - 86°C) (FH06/09/12)/167 - 176°F
(75 - 80°C) (FH15/18) or temperature of P.C. board tempera-
ture thermistor on the inverter P.C.board exceeds 162 - 185°F
(72 - 85°C) (FH06/09/12)/158 - 167°F (70 - 75°C) (FH15/18).
Check around outdoor unit.
Check outdoor unit air passage.
Refer to 10-5.
"Check of outdoor
fan motor".
11
5-time ash
2.5 seconds OFF
High pressure pro-
tection
Indoor coil thermistor exceeds 158°F (70°C) in HEAT mode.
Defrost thermistor exceeds 158°F (70°C) in COOL mode.
Check refrigerant circuit and refrig-
erant amount.
Check stop valve.
12
8-time ash
2.5 seconds OFF
Compressor syn-
chronous abnormal-
ity
The waveform of compressor current is distorted.
Reconnect connector of compressor.
Refer to 10-5.
"How to check
inverter/compressor".
13
10-time ash
2.5 seconds OFF
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Refer to 10-5.
"Check of outdoor
fan motor.
Refer to 10-5.
"Check of inverter
P.C. board.
14
12-time ash
2.5 seconds OFF
Each phase current
of compressor
Each phase current of compressor cannot be detected nor-
mally.
Refer to 10-5.
"How to check
inverter/compressor".
15
13-time ash
2.5 seconds OFF
DC voltage DC voltage of inverter cannot be detected normally.
It occurs with following case.
Instantaneous power voltage
drop. (Short time power failure)
(FH15/18)
Refer to 10-5.
"Check of power
supply". (FH15/18)
Refer to 10-5.
"How to check in-
verter/compressor".
NOTE: 1. The location of LED is illustrated at the right gure. Refer to 10-6.1.
2. LED is lighted during normal operation.
The ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the ashing frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
LED
Flashing
MUZ-FH06/09/12NA(H)
Inverter P.C. board
MUZ-FH15/18NA(H)
LED
Flashing