MUZ-FH Service
15
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: ft. Piping size O.D: in.
Max. Length
A
Max. Height difference
B
Gas Liquid
MUZ-FH06NA
MUZ-FH06NAH
MUZ-FH09NA
MUZ-FH09NAH
MUZ-FH12NA
MUZ-FH12NAH
65 40 3/8 1/4
MUZ-FH15NA
MUZ-FH15NAH
MUZ-FH18NA
MUZ-FH18NAH
MUZ-FH18NA2
MUZ-FH18NAH2
100 50 1/2 1/4
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 65
MUZ-FH06NA
MUZ-FH06NAH
MUZ-FH09NA
MUZ-FH09NAH
2 lb. 9 oz. 0 1.08 3.24 5.40 7.56 8.64
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 65
MUZ-FH12NA
MUZ-FH12NAH
2 lb. 9 oz. 0 1.62 4.86 8.10 11.34 12.96
Calculation: X oz. = 1.62/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 70 80 90 100
MUZ-FH15NA
MUZ-FH15NAH
MUZ-FH18NA
MUZ-FH18NAH
MUZ-FH18NA2
MUZ-FH18NAH2
3 lb. 7 oz. 0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)