Sales Fact Sheet

45
The upper
lamp of the
OPERATION
INDICATOR
lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition Remedy
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit
failure mode
recall function
10-time ash
2.5 seconds
OFF
Discharge temperature
Temperature of discharge temperature
thermistor has been 122°F (50°C) or
less for 20 minutes.
Refer to 10-5.
"Check
of LEV".
Check refrigerant
circuit and refrigerant
amount.
11-time ash
2.5 seconds
OFF
DC voltage 8-time ash
2.5 seconds OFF
DC voltage of inverter cannot be
detected normally.
Refer to 10-5.
"How
to check inverter/
compressor".
Each phase current of
compressor
9-time ash
2.5 seconds OFF
Each phase current of compressor
cannot be detected normally.
14-time ash
or more
2.5 seconds
OFF
Stop valve (Closed valve) 14-time ash
2.5 seconds OFF
Closed valve is detected by
compressor current.
Check stop valve.
○○
4-way valve/
Pipe temperature
16-time ash
2.5 seconds OFF
The 4-way valve does not work
properly.
The indoor coil thermistor detects an
abnormal temperature.
Check the 4-way
valve.
Replace the inverter
P.C. board.
Outdoor refrigerant system
abnormality
1-time ash
2.5 seconds OFF
A closed valve and air trapped in the
refrigerant circuit are detected based
on the temperature sensed by the
indoor and outdoor thermistors and the
current of the compressor.
Check for a gas leak
in a connecting piping
etc.
Check the stop valve.
Refer to 10-5.
“Check of outdoor
refrigerant circuit”.
○○
NOTE: Blinking patterns of this mode differ from the ones of
TROUBLESHOOTING CHECK TABLE (10-3.).
OBH733D