Sales Fact Sheet

24
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 70 80 90 100
MUZ-GL18NA
MUZ-GL18NAH
MUY-GL18NA
3 lb. 9 oz. 0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
NOTE: Refrigerant piping exceeding 33 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
33 40 50 60 70 80 90 100
MUZ-GL24NA
MUZ-GL24NAH
MUY-GL24NA
4 lb. 3 oz. 0 4.14 10.06 15.98 21.90 27.82 33.74 39.66
Calculation: X oz. = 2.96/5 oz./ft. × (Refrigerant piping length (ft.) - 33)
OBH733D