MXZ-SM36NAM Submittal

Specications are subject to change without notice. © 2022 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
SPECIFICATIONS: MXZ-SM36NAM-U1
test
Cooling
1
(Non-Ducted // Mix // Ducted)
Maximum Capacity BTU/H 36,000 // 36,000 // 36,000
Rated Capacity BTU/H 36,000 // 36,000 // 36,000
Minimum Capacity BTU/H 15,500 // 15,500 // 15,500
Maximum Power Input W 2,400 // 2,610 // 2,855
Rated Power Input W 2,400 // 2,610 // 2,855
Power Factor (208V, 230V) % 98.5, 98.5 // 98.5, 98.5 // 98.5, 98.5
Heating at 47°F
2
(Non-Ducted // Mix //
Ducted)
Maximum Capacity BTU/H 42,000 // 42,000 // 42,000
Rated Capacity BTU/H 42,000 // 42,000 // 42,000
Minimum Capacity BTU/H 22,500 // 22,500 // 22,500
Maximum Power Input W 3,080 // 3,200 // 3,325
Rated Power Input W 3,080 // 3,200 // 3,325
Power Factor (208V, 230V) % 98.5, 98.5 // 98.5, 98.5 // 98.5, 98.5
Heating at 17°F
3
(Non-Ducted // Mix //
Ducted)
Maximum Capacity BTU/H 29,400 // 29,400 // 29,400
Rated Capacity BTU/H 26,400 // 26,400 // 26,400
Maximum Power Input W 3,910 // 4,000 // 2,400
Rated Power Input W 2,760 // 2,825 // 2,890
Heating at 5°F
4
(Non-Ducted // Mix //
Ducted)
Maximum Capacity BTU/H 25,200 // 25,200 // 25,200
Maximum Power Input W 3,360 // 3,535 // 3,710
Efciency (Non-Ducted // Mix // Ducted)
SEER 23.0 // 20.65 // 18.3
EER
1
15.0 // 13.8 // 12.6
HSPF (IV) 12.5 // 11.8 // 11.2
COP at 47°F
2
4.0 // 3.85 // 3.7
COP at 17°F at Maximum Capacity
3
2.2 // 2.15 // 2.1
COP at 5°F at Maximum Capacity
4
2.2 // 2.1 // 2.0
ENERGY STAR
®
Certied Yes // No // Yes
Electrical
Voltage, Phase, Frequency 208/230, 1, 60
Guaranteed Voltage Range V AC 187-253
Voltage: Indoor - Outdoor, S1-S2 V AC 208/230
Voltage: Indoor - Outdoor, S2-S3 V DC 24
Short-circuit Current Rating (SCCR) kA 5
Recommended Fuse/Breaker Size if Branch Box Powered by
Outdoor Unit
A 40
Recommended Fuse/Breaker Size without Branch Box or Branch
Box Powered Separate
A 30
Recommended Wire Size (Indoor - Outdoor) AWG 16
MCA if Branch Box Powered by Outdoor Unit A 35.0
MCA without Branch Box or Branch Box Powered Separate A 29
MOCP if Branch Box Powered by Outdoor Unit A 50
MOCP without Branch Box or Branch Box Powered Separate A 40
Fan Motor Full Load Amperage A 0.6+0.6
Fan Motor Output W 74
Outdoor unit
Airow Rate (Cooling / Heating) CFM 3,885 / 3,885
Refrigerant Control LEV
Defrost Method Reverse Cycle
Heat Exchanger Type Plate n coil
Heat Exchanger Coating Blue Fin Coating
Sound Pressure Level,Cooling
1
dB(A) 49
Sound Pressure Level,Heating
2
dB(A) 53
Compressor Type Hermetic
Compressor Model ANB33FNHMT
Compressor Motor Output kW 2.8
Compressor Rated Load Amps A 19
Compressor Locked Rotor Amps A 22.0
Compressor Oil Type // Charge oz. FV50S // 78
Base Pan Heater Optional (PAC-SJ20BH-E)
Unit Dimensions
W: In. [mm] 41-11/32[1,050]
D: In. [mm] 13[330]
H: In. [mm] 52-11/16[1,338]
Package Dimensions
W: In. [mm] 43 [1,090]
D: In. [mm] 18 [450]
H: In. [mm] 57 [1,430]
Unit Weight Lbs.[kg] 271 [123]
Package Weight Lbs.[kg] 295 [134]
NOTES:
AHRI Rated Conditions
1
Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
(Rated data is determined at a xed compressor speed)
2
Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
3
Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
Conditions
4
Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB
*
Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
*A
when 1 or more PLA-A·EA7 connected
*B
Branch box should be placed within the level between the outdoor unit and indoor units
*C
5°F DB - 115°F DB when optional wind bafes are installed
For actual capacity performance based on indoor unit type and number of indoor units connected, please refer to MXZ Operational Performance.
Although the maximum connectable capacity is 130%, the outdoor unit cannot provide more than 100% of the rated capacity. Please utilize this over capacity capability for load shedding or applications
where it is known that all connected units will NOT be operating at the same time.