Engineering Manual

B-74
Current ( 208V) Current ( 230V)
1 unit 2 unit 3 unit 4 unit 1 unit 2 unit 3 unit 4 unit
6 4.4 6 4.0
9 4.5 9 4.1
12 5.0 4.8 12 4.5 4.3
15 5.2 5.0 15 4.7 4.5
18 7.3 7.0 6.5 18 6.6 6.4 5.9
21 9.3 8.7 7.7 21 8.4 7.9 7.0
24 11.4 10.4 9.7 9.4 24 10.3 9.4 8.8 8.5
27 12.0 11.5 11.2 27 10.9 10.4 10.1
30 13.9 13.0 13.6 30 12.6 11.7 12.3
33 13.7 14.2 15.6 33 12.4 12.8 14.1
36 13.5 14.7 17.9 36 12.2 13.3 16.2
39 15.2 18.1 39 13.8 16.3
42 15.0 18.0 42 13.6 16.3
Current ( 208V) Current ( 230V)
1 unit 2 unit 3 unit 4 unit 1 unit 2 unit 3 unit 4 unit
6 6
9 4.8 9 4.3
12 5.4 12 4.9
15
6 9
15
6 3
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
0369 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60
Cooling - NonDuct
1 unit
2 unit 3 unit
4 unit
16.0
18.0
20.0
Cooling - Duct
1 unit
2 unit
3 unit
4 unit
Current (A)
Total capacity of indoor units (kBTU/h)
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
0369 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60
Cooling - NonDuct
1 unit
2 unit
3 unit
4 unit
14 0
16.0
18.0
Cooling - Duct
1 unit
2 unit
3 unit
4 unit
Current (A)
Total capacity of indoor units (kBTU/h)
15
6
.
9
15
6
.
3
18 9.0 8.7 18 8.1 7.8
21 10.7 10.1 21 9.7 9.1
24 11.9 11.4 24 10.8 10.3
27 12.7 11.9 27 11.5 10.8
30 14.3 14.5 30 12.9 13.1
33 14.2 15.3 33 12.8 13.8
36 14.1 16.1 18.0 36 12.7 14.6 16.3
39 15.9 18.0 39 14.4 16.3
42 15.7 18.0 42 14.2 16.3
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18
.
0
0369 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16
.
0
0369 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60
Capacity (Cooling - NonDuct) Input ( Cooling - NonDuct)
1 unit 2 unit 3 unit 4 unit 1 unit 2 unit 3 unit 4 unit
6 6000 6 870
9 9000 9 890
12 12000 12000 12 980 960
15 14000 15000 15 1020 1000
18 17200 18000 18000 18 1440 1420 1320
21 19800 20000 21000 21 1840 1760 1560
24 22500 23000 24000 24000 24 2250 2100 1960 1940
27 25800 26000 27000 27 2420 2310 2300
30 28000 28400 30000 30 2800 2620 2790
33 28000 32000 32000 33 2760 2860 3210
36 28000 32000 35400 36 2720 2970 3680
39 32000 36000 39 3070 3720
42 32000 36000 42 3030 3700
Ca
pacity (Cooling - Duct)
Input ( Cooling - Duct)
1 unit 2 unit 3 unit 4 unit 1 unit 2 unit 3 unit 4 unit
6 6
9 9000 9 940
12 12000 12 1070
15
15000
15
1370
0
5000
10000
15000
20000
25000
30000
35000
40000
0369 12 15 18 21 24 27 3033 36 39 4245 4851 54 57 60
Cooling - NonDuct
1 unit 2 unit
3 unit 4 unit
35000
40000
Cooling - Duct
1 unit 2 unit
3 unit
4 unit
Capacity (kBTU/h)
Total capacity of indoor units (kBTU/h)
0
500
1000
1500
2000
2500
3000
3500
4000
0369 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60
Cooling - NonDuct
1 unit 2 unit
3 unit 4 unit
3500
4000
Cooling - Duct
1 unit 2 unit
3 unit 4 unit
Input (W)
Total capacity of indoor units (kBTU/h)
15
15000
15
1370
18 17200 18000 18 1770 1750
21 20600 21000 21 2110 2040
24 24000 24000 24 2360 2300
27 26200 27000 27 2560 2410
30 28000 30000 30 2880 2920
33 28000 32000 33 2860 3080
36 28000 32000 34400 36 2840 3250 3700
39 32000 34800 39 3210 3700
42 32000 35200 42 3170 3700
0
5000
10000
15000
20000
25000
30000
0369 12 15 18 21 24 27 3033 36 39 4245 4851 54 57 60
0
500
1000
1500
2000
2500
3000
0369 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60
NOTE 1: When 2 or more indoor units are running, the capacity
per unit is obtained based on the capacity ratio of their
individual operation.
NOTE 2: Input for the indoor unit is excluded.
MXZ-4C36NA2