Service Manual

81
3. Table of outdoor unit failure mode recall function
The left lamp of
OPERATION IN-
DICATOR lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C.
board)
Condition Remedy
Indoor/
outdoor unit
failure mode
recall function
LED 1 LED 2
OFF None (Normal) Lighted Lighted
2-time ash Outdoor power system Lighted Lighted Overcurrent protection cut-out operates
3 consecutive times within 1 minute after
the compressor gets started, or converter
protection cut-out or bus-bar voltage
protection cut-out operates 3 consecutive
times within 3 minutes after startup.
• Check the connection of the com-
pressor connecting wire.
• Refer to 11-6.
"How to check inverter/compres-
sor".
• Check the stop valve.
3-time ash Discharge temperature thermistor
Lighted Once
A thermistor shorts or opens during
compressor running.
• Refer to 11-6. "Check of outdoor
thermistors".
Defrost thermistor
Lighted Once
Ambient temperature thermistor
Lighted Twice
Fin temperature thermistor
Lighted 3 times
P.C. board temperature thermistor
Lighted 4 times
• Replace the outdoor control P.C. board.
Outdoor heat exchanger tem-
perature thermistor
Lighted 9 times • Refer to 11-6. "Check of outdoor
thermistors".
4-time ash Overcurrent Once Not
lighted
18A (MXZ-2C20NA2)/21 A (MXZ-3C24/3C30/4C36NA,
MXZ-3C24/3C30/4C36NA2)/28 A (MXZ-5C42NA,
MXZ-2C20/3C24/3C30NAHZ, MXZ-5C42NA2, MXZ-
2C20/3C24/3C30NAHZ2) current ows into power module.
• Reconnect compressor connector.
• Refer to 11-6.
"How to check in-
verter/compressor".
• Check the stop valve.
5-time ash Discharge temperature Lighted Lighted
The discharge temperature exceeds 239°F (MXZ-
2C20NA2)/222.8°F (MXZ-3C24/3C30/4C36NA,
MXZ-3C24/3C30/4C36NA2)/240.8°F (MXZ-2C20
/3C24/3C30NAHZ, 5C42NA, MXZ-2C20/3C24
/3C30NAHZ2, 5C42NA2) during operation.
Compressor can restart if discharge temperature
thermistor reads 176°F (MXZ-2C20NA2)/203°F
(MXZ-3C24/3C30/4C36NA, MXZ-3C24/3C30
/4C36NA2)/212°F (MXZ-2C20/3C24/3C30NAHZ,
5C42NA, MXZ-2C20/3C24/3C30NAHZ2, 5C42NA2)
or less 3 minutes later.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-6.
"Check of LEV".
6-time ash High pressure Lighted Lighted
The outdoor heat exchanger temperature ex-
ceeds 158°F during cooling or the indoor gas
pipe temperature exceeds 158°F during heating.
• Check refrigerant circuit and refrig-
erant amount.
• Check the stop valve.
7-time ash Fin temperature 3 times Not
lighted
The n temperature exceeds 190°F (MXZ-3C24/3C30/
4C36NA, MXZ-2C20/3C24/3C30/4C36NA2)/192°F
(MXZ-2C20/3C24/3C30NAHZ, 5C42NA, MXZ-2C20/
3C24/3C30NAHZ2, 5C42NA2) during operation.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 11-6.
"Check of outdoor
fan motor".
P.C. board temperature 4 times Not
lighted
The P.C. board temperature exceeds 152°F (MXZ-
3C24/3C30/4C36NA, MXZ-2C20/3C24/3C30/
4C36NA2)/189°F (MXZ-2C20/3C24/3C30NAHZ,
MXZ-5C42NA, MXZ-2C20/3C24/3C30NAHZ2,
5C42NA2) during operation.
8-time ash Outdoor fan motor Lighted Lighted A failure occurs 3 consecutive times within
30 seconds after the fan gets started.
• Refer to 11-6. "Check of outdoor
fan motor".
9-time ash Outdoor control system Lighted 5 times Nonvolatile memory data cannot be read
properly.
• Replace the outdoor control P.C.
board.
10-time ash Low discharge temperature
protection
Lighted Lighted
The frequency of the compressor is kept 80
Hz or more and the discharge temperature is
kept under 102.2°F for more than 20 minutes.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-6.
"Check of LEV".
11-time ash Communication error
between P.C. boards
Lighted 6 times
Communication error occurs between the out-
door control P.C. board and outdoor power P.C.
board for more than 10 seconds.
• Check the connecting wire between
outdoor control P.C. board and out-
door power P.C. board.
The communication between boards protec-
tion cut-out operates 2 consecutive times.
Current sensor Lighted 7 times
A short or open circuit is detected in the cur-
rent sensor during compressor operating.
Current sensor protection cut-out oper-
ates 2 consecutive times.
Zero cross detecting circuit 5 times Not
lighted
Zero cross signal cannot be detected
while the compressor is operating.
• Check the connecting wire among
outdoor control P.C. board and out-
door power P.C. board.
The protection cut-out of the zero cross de-
tecting circuit operates 10 consecutive times.
Converter 5 times Not
lighted
A failure is detected in the operation of the
converter during operation.
• Check the voltage of power supply.
• Replace the outdoor power P.C.
board.
Bus-bar voltage 5 times Not
lighted
The bus-bar voltage exceeds 400 V or
falls to low level during compressor oper-
ating.
• Check the voltage of power supply.
Replace the outdoor power P.C. board
or the outdoor control P.C. board.
15-time ash LEV and drain pump Lighted Lighted The indoor unit detects an abnormality in
the LEV and drain pump.
• Refer to 11-6. "Check of LEV".
• Check the drain pump of the indoor unit.
NOTE: Blinking patterns of this mode differ from the ones of
TROUBLESHOOTING CHECK TABLE (11-4.).
OBH702F