Be sure to use the analog voltmeter for measurement.
With the connector between compressor and IPM disconnected, activate the inverter and measure the balance of voltage between terminals.
<< Operation method>>
Start heating operation by pressing the EMERGENCY OPERATION switch
on the indoor unit. (test-run mode)
<<Measurement point>>
at 3 points
BLK-WHT
BLK-RED
WHT-RED
<<Judgment>>
Balanced································normal
Unbalanced···························abnomal (open phase)
Shutdown by overcurrent·······abnormal (short)
NOTE 1. Measure AC voltage, at 3 points more than one minute after the outdoor fan motor starts running.
2. The output voltage values in above table have tolerance withinJi20%.
w Measure AC voltage between
the lead wires at 3 points.
ACV
300
ACV
300
ACV
300
ACV
300
ACV
300
ACV
300
Normal
(Balanced)
Abnormal
(unbalanced)
BLK-WHT BLK-RED WHT-RED
BLK-WHT BLK-RED WHT-RED
Voltmeter indication
COOL
HEAT
120
130
110
Operational
frequency
[Hz]
Operation
mode
Model
MSZ09UN
MSZ12UN
MSZ09UN
MSZ12UN
Output
voltage
[V]
64
70
58
Disconnect the connector between compressor and IPM, and
measure resistance between terminals on the IPM.
<<Measurement point>>
at 6 points
BLK-WHT, WHT-BLK
BLK-RED, RED-BLK
WHT-RED, RED-WHT
<<Judgment>>
Infinite ["]···········normal
0~dozens of ······abnormal (short)
w Measure resistance between
the lead wires at 3 points
ohmmeter indication
normal
(infinite)
abnormal
(0~dozens of ")
X1
"
X1
"
Check of open phase
B
Check of open IPM
C
Check the voltage
between terminals.
Check the
compressor.
Disconnect the connector
between compressor and
IPM.
Refer to D “Check of compressor” on page 48.
No
Refer to B “Check of open phase” on page 47.
Replace the outdoor
electronic control P.C.
board.
Yes
Are voltages
balanced?
How to check inverter/ compressor
A
When OPERATION INDICATOR lamp flashes 5-time.
Outdoor unit does not operate.