Service manual
43
1. Troubleshooting check table
Operation Indicator
flashing
· Flashing of the OPERATION INDICATOR lamp (on the left-hand side) 
 indicates possible abnormalities.
· The OPERATION INDICATOR lamp (on the left-hand side) is lighted during 
 normal operation.
• The following indication applies regardless of shape of the indicatior.
· Flashing of the operation indicator lamp (on the left-hand side) indicates possible abnormalities.
· The operation indicator lamp (on the left-hand side) is lighted during normal operation.
No.
1
2
3
5
6
7
Symptom
Operation indicator lamp
Abnormal point Detection method Checkpoint
Outdoor unit 
does not 
operate.
repeated flashes 
every 0.5 seconds
1-time flash
2.5 seconds OFF
2-time flash
2.5 seconds OFF
5-time flash
2.5 seconds OFF
Mis-Wiring
Serial signal
Outdoor power 
system
6-time flash
2.5 seconds OFF
Outdoor 
thermistors
7-time flash 
2.5 seconds OFF
Outdoor control 
system
Indoor coil 
thermistor 
Auxiliary indoor 
coil thermistor
Room 
temperature 
thermistor
When the unit operates by the remote controller or 
emergency operation switch at 3 minutes after the main 
power supply is turned on.
3 minutes after power supply turns ON, when serial signal is 
not received.
When indoor electronic control P.C. board does not 
receive serial signals from outdoor unit for 4 to 5 
seconds,
Indoor electronic control P.C. board constantly 
detects resistance every 8 seconds.
When thermistor shorts or opens.
When compressor has stopped due to overcurrent 
protection or start-up failure protection 3 times in a 
row within 1 minute after start-up.
<Thermistor short>
Thermistors are abnormal when they short after 
compressor start-up.
<Thermistor open>
Thermistors are abnormal when they open after 
compressor start-up.
Discharge temperature thermistor is abnormal when 
open circuit is detected more than 10 minutes after 
compressor start-up.
Defrost thermistor is abnormal when open circuit is 
detected more than 1 minutes after compressor 
start-up.
When nonvolatile memory data cannot be read properly 
on outdoor control P.C. board, outdoor unit stops and 
restarts 3 minutes later.
· Shortage of 
refrigerant
· Outdoor electronic 
control P.C. board
 Refer to J "Check 
of outdoor 
thermistors" on 
page 51.
Refer to the 
characteristics of main 
indoor coil thermistor, 
sub indoor coil 
thermistor, and room 
temperature thermistor 
on page 56 or 57.
Refer to A "How to 
check inverter/ 
compressor" on page 
47.
Replace outdoor 
electronic control P.C. 
board.
Refer to 'Checking 
serial signal error' on 
page 55.
4
3-time flash
2.5 seconds OFF
Indoor fan motor
When rotational frequency feedback signal is not 
emit during 12-second indoor fan operation.
Refer to G "Check of 
indoor fan motor" on 
page 49.
Indoor fan 
motor repeats 
12 seconds 
ON and 3 
minutes OFF. 
When the 
indoor fan 
motor breaks, 
the fan keeps 
stopping.
Outdoor unit 
does not 
operate.
When the indoor unit has started operation and the above detection method has detected an abnormality (the first 
detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with the 
OPERATION INDICATOR lamp flashing.