50
I Check of outdoor fan motor
Is the resistance of outdoor fan motor normal?
(Refer to 11-4.)
Replace the outdoor fan motor.
Replace the inverter P.C. board.
No
Yes
Disconnect CN932 from the inverter P.C. board,
and measure the resistance of the outdoor fan
motor.
MUZ-GE25VA MUZ-GE25VAH MUZ-GE35VA MUZ-GE35VAH MUZ-GE42VA MUZ-GE42VAH
Is the resistance between each ter-
minal of outdoor fan motor normal?
(Refer to 11-4.)
Disconnect CN932 from the inverter P.C. board, and turn on the
power supply.
Rotate the outdoor fan motor manually and measure the voltage
of CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
Does the voltage between each terminal become 5 and 0
VDC repeatedly?
Does the outdoor fan motor rotate smoothly?
Replace the outdoor fan motor.
Replace the inverter P.C. board.
Yes
Yes
No
(Fixed to either 5 or 0 VDC)
No
No
Yes
MUZ-GE50VA MUZ-GE50VAH MUZ-GE60VA MUZ-GE71VA
Disconnect the connectors CN931
and CN932 from the inverter P.C.
board.
Check the connection between the
connector CN931 and CN932.