LED1 LED2
OFF Normal
11-time flash
Converter Communication error
between P.C. boards
Lighting 6 times When the communication between
boards protection stop is
continuously performed twice.
Check the connecting wire
between outdoor electronic control
P.C. board and power board.
Communication between P.C.
boards protection
Lighting 6 times Communication error occurs
between the electronic control P.C.
board and power board for more
than 10 seconds.
Current sensor Lighting 7 times Current sensor protection stop is
continuously performed twice.
Replace the power board.
Current sensor protection Lighting 7 times When a short or open circuit is
detected in the current sensor
during compressor operating.
Zero cross detecting circuit 5 times Goes
out
The protection stop of the zero
cross detecting circuit is
continuously performed 10 times.
Check the connecting wire among
electronic control P.C. board, noise
filter P.C. board and power board.
Zero cross detecting circuit
protection
5 times Goes
out
When zero cross signal cannot be
detected while the compressor is
operating.
Converter protection 5 times
Goes
out
When a failure is detected in the
operation of the converter during
operation.
Replace the power board.
Bus-bar voltage
protection (1)
5 times When the bus-bar voltage exceeds
400V or falls to 200V or below
during compressor operating.
Bus-bar voltage
protection (2)
wEven if this protection stop is
performed continuously three
times, it does not mean the
abnormality in outdoor power
system.
6 times When the bus-bar voltage exceeds
400V or falls to 50V or below during
compressor operating.
Indoor operation
indicator lamp
Abnormal point
(Failure mode)
Details of abnormal point Detecting method Check point
Indoor/outdoor
failure mode
recall function
Outdoor LED indication
-
-
-
-
Goes
out
Goes
out
-
OB389 --1qxp 05.1.26 18:14 Page 29