Service manual

34
Primary current protection
Secondary current protection
High-pressure protection
Defrosting in cooling
3 times
Lighting
Discharge temperature
protection
Check refrigerant circuit and refrigerant amount.
Refer to 11-6.D "Check of LEV".
Refer to 11-6.F "Check of outdoor thermistors".
4 times
Lighting
Low discharge temperature
protection
Refer to 11-6.D "Check of LEV".
Check refrigerant circuit and refrigerant amount.
5 times
Lighting
Cooling high-pressure protection
This symptom does not mean any abnormality of the product,
but check the following points.
Check if indoor filters are clogged.
Check if refrigerant is short.
Check if indoor/outdoor unit air circulation is short cycled.
-
-
These symptoms do not mean any abnormality of the product,
but check the following points.
Check if indoor filters are clogged.
Check if refrigerant is short.
Check if indoor/outdoor unit air circulation is short cycled.
Twice Lighting
Once Lighting
The discharge temperature exceeds 100: during operation.
The frequency of the compressor is kept 80Hz or more and the discharge
temperature is kept under 39: for more than 20 minutes.
The outdoor heat exchanger temperature exceeds 58: during operation.
9 times
Lighting
Inverter check mode
Lighting
Lighting
Normal
The unit is operated with emergency operation switch.
-
The input current exceeds 15A.
The current of the compressor exceeds 15A.
The indoor gas pipe temperature exceeds 45: during heating.
The indoor gas pipe temperature falls 3: or below during cooling.
LED1(Red) LED2(Yellow)
Abnormal point / Condition Correspondence
Indication
Condition
Outdoor unit
operates.
Outdoor unit
operates
No.
Symptom
20
21
22
23
24
25
26
OB389F--2qxp 07.9.3 5:08 PM Page 34