Service manual

37
Outdoor unit does not operate at all, or stops immediately due to overcurrent.
Check of LEV (Expansion valve)
Check of current-limiting resistor
K
L
Heating/Cooling does not work sufficiently.
When the current-limiting resistor is open, the rush current limiting relay (X64) may not work properly.
Check other electric parts in the main circuit together in the case that the current-limiting resistor is defective.
Turn ON the power
supply and press
EMERGENCY
OPERATION switch.
Replace the inverter P.C.
board or the compressor.
Replace the power P.C.
board or the inverter P.C.
board.
Does the rush current
limiting relay(X64) work
properly? (Normally it
closes 1 second after
outdoor unit power ON.)
No
Yes
No
No
Yes
Yes
Is the resistance of current-limiting
resistor (R64A or R64B) on the
power P.C. board normal?
(Normal resistance : 5' i5%)
Replace the power P.C.board.
Replace the power P.C. board.
Does LED on the inverter
P.C. board light up?
Replace the LEV.
Expansion valve operates in
full-opening direction.
Is LEV properly fixed to the
expansion valve?
Ok
Do you hear the expansion
valve "click, click·······"?
Do you feel the expansion
valve vibrate on touching it ?
Does the resistance of LEV
have the characteristics?
Refer to 11-5.
Measure each voltage between connector pins
of CN724 on the inverter P.C. board.
1.Pin3(-) Pin1(+)
2.Pin4(-) Pin1(+)
3.Pin5(-) Pin1(+)
4.Pin6(-) Pin1(+)
Is there about 3~5V AC between each?
NOTE: Measure the voltage by an analog tester.
No
Yes
Yes
Yes
No
Replace the
expansion valve.
Yes
No
No
Properly fix the LEV to the
expansion valve.
Replace the
inverter P.C. board.
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON it again.
2. Press RESET button on the remote controller.
W1. Regardless of normal or abnormal condition,
a short beep is emitted once the signal
is received.
Turn ON the power supply.
<
Preparation of the remote controller
>
1 While pressing both OPERATION SELECT
button and TOO COOL button on the remote
controller at the same time, press RESET button.
2 First, release RESET button.
And release the other two buttons after all LCD
except the set temperature in operation display
section of the remote controller is displayed after
3 seconds.
Press OPERATE/STOP(ON/OFF) button of the remote
controller (the set temperature is displayed) with the
remote controller headed towards the indoor unit. W1
OB372D --2qxp 07.5.7 4:49 PM Page 37