Service manual

21
Check of indoor fan motor
A
When POWER lamp flashes 3-time.
Indoor fan does not operate.
w If more than 12 seconds passes after EMERGENCY OPERATION switch
is pressed, the voltage mentioned above 2 goes 0V DC although the
indoor electric control P.C. board is normal.
Indoor electronic
control P.C. board
Pay careful attention to the high voltage on
the fan motor connector CN211.
Yes
No
No
No
(Changed)
Yes
(Unchanged)
Is there any foreign matter that
interferes the rotation of the
line flow fan?
Turn OFF the power supply.
Remove the foreign matter and
adjust the line flow fan.
Turn ON the power supply, wait 5 seconds or more, and then press
EMERGENCY OPERATION switch.
Measure the supply voltage as follows within 12 seconds
after EMERGENCY OPERATION switch is pressed.
If more than 12 seconds passes by, turn OFF the power supply and
turn ON it again, then measure the voltage. w
1.Measure the voltage between CN211 1(+) and 3(-).
2.Measure the voltage between CN211 5(+) and 3(-).
Is there 325V DC between
CN211 1 (+) and 3 (-), and does 
the voltage between CN211 5(+)
and 3(-) rise to the range of 3 to 6V
DC within 12 seconds after 
EMERGENCY OPERATION switch 
is pressed?
Yes
Replace the indoor fan motor.
CN211
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between CN211
6(+) and 3(-) while the fan
motor is rotating.
Is it unchanged holding
0V DC or 15V DC?
Replace the indoor fan motor.
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan doesn't operate.
9-6. Troubleshooting flow