Service manual

15
2. Flow chart of PLASMA DEODORIZING/PLASMA AIR PURIFYING power failure mode recall function
Operational procedure
Note1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2.Blinking pattern when plasma unit is abnormal:
Yes
(Blinks)
No
(OFF)
W1. Regardless of normal or abnormal, a short
beep is emitted as the signal is received.
Does POWER lamp on the indoor
unit blink at the interval of 0.5 seconds?
Blinks: The plasma unit is abnormal.
Beep are emitted at the same timing as the 
blinking of POWER lamp. W2
Deleting the abnormal memorized condition
Repair the defective parts.
With the remote controller headed towards the indoor unit, press TOO COOL or TOO
WARM button to adjust the set temperature to 23:. W1
The plasma unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. (A or B C)
AWith the remote controller headed towards the indoor unit, press any button
that is not used in this failure mode recall function (e.g. TIMER button) .
BTurn OFF the power supply and turn ON it again.
CPress RESET button of the remote controller.
The plasma unit is abnormal.
Check the blinking pattern, and refer to confirm the
abnormal point with the PLASMA DEODORIZING/PLASMA AIR 
PURIFYING power failure mode table (9-2.5.).
Make sure to check at least two consecutive blinking cycles. W2
Release the failure mode recall function according to the left 
mentioned procedure.
Confirm that the remote controller is in the failure mode recall
function.
The plasma unit might be abnormal.
Confirm if plasma unit is abnormal according to the following procedures.
ON
OFF
Beeps
Repeated cycle Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
Beeps
1After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) 
with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
4Release the failure mode recall function according to "Releasing the failure mode recall function" 
mentioned above.
3. PLASMA DEODORIZING/PLASMA AIR PURIFYING power operation check
NOTE: Perform the above mentioned check with the front panel closed (Refer to 9-1.6 Figure5). The SAFETY DEVICE
(PLASMA UNIT) works by opening front panel and the plasma power is cut.
ActionPLASMA/WASH lamp
Continuously blinking
2-time flash
Follow "Check of
PLASMA DEODORIZING
power" or "Check of
PLASMA AIR PURIFYING
power" 
to identify the error.(Refer to 9-6.F or G.)
PLASMA DEODORIZING power and/or PLASMA AIR PURIFYING power
control circuit on the indoor 
electronic control P.C. board is out of order.(Refer to 9-6.F or G.)
PLASMA DEODORIZING/PLASMA AIR PURIFYING power goes ON when PLASMA button on the remote contoller is pressed
with any set temperature displayed during failure mode recall function.
PLASMA button is pressed, the power of plasma is changed in sequence:
PLASMA DEODORIZING power goes ON PLASMA AIR PURIFYING power goes ON Cancel
Check the operation display section of the remote controller to confirm that PLASMA DEODORIZING power or PLASMA AIR 
PURIFYING power is activated.
While PLASMA/WASH lamp stays OFF, it means normal.
Flashing PLASMA/WASH lamp means abnormal, the plasma power is not conducted.