Service manual
4
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance (at 20:)
Model
Winding
resistance (at 20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity (R410A)
Refrigeration oil (Model)
kW
R/h
K /h
A
A
W
A(kW)
%
A
A
A
W
"
"
mm
kg
dB
rpm
kg
cc
MUH-GA25VB
-
E2
Single phase
230V,50Hz
1,902
10
—
19
0.33
KN104VTMHC
700
C-R 3.62
C-S 5.40
RA6V33-KB
WHT-BLK 215
BLK-RED 307
800o550o285
30
49
855
1
0.65
350 (NEO22)
Cooling
2.65
1.1
3.43
785
100
3.10
3.23
Heating
3.0
—
3.43
785
100
3.10
3.66
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance (C.O.P)
Outdoor unit power supply
Function
Outdoor model
MUH-GA25VB
-
E1
Single phase
230V,50Hz
1,902
10
—
22
0.33
RN104VHSHT
700
C-R 3.40
C-S 4.56
RA6V33-KB
WHT-BLK 215
BLK-RED 307
800o550o285
32
49
855
1
0.80
350 (NEO22)
Cooling
2.65
1.1
3.43
785
100
3.10
3.23
Heating
3.0
—
3.43
785
100
3.10
3.66
MUH-GA35VB
-
E1
Single phase
230V,50Hz
1,902
10
—
27
0.33
RN135VHSHT
900
C-R 2.79
C-S 3.36
RA6V33-KB
WHT-BLK 215
BLK-RED 307
800o550o285
35
49
855
1
0.80
620 (NEO22)
Cooling
3.5
1.7
4.65
1,050
98
4.32
3.21
Heating
3.7
—
4.34
980
98
4.01
3.63
MUH-GA35VB
-
E3
Single phase
230V,50Hz
1,902
10
—
27
0.33
RN135VHSHT
900
C-R 2.79
C-S 3.36
RA6V33-KB
WHT-BLK 215
BLK-RED 307
800o550o285
39
49
855
1
1.05
620 (NEO22)
Cooling
3.5
1.7
4.65
1,050
98
4.32
3.21
Heating
3.7
—
4.34
980
98
4.01
3.63
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C Heating : Indoor DB20°C
Outdoor DB35°C WB24°C Outdoor DB 7°C/WB 6°C
Indoor-Outdoor piping length : 5m
OB387B-1.qxp 07.5.23 2:48 PM Page 4