Instruction manual
92
Options
4.2.2 Preferences
Setting of the model check at parameter batch write, test operation setting and batch parameter write setting are available.
Click of the "Option" window to display the Preferences window.
No. Name Function and description
A
Enable model check
When checked, inverter models, voltage classes, capacities and region codes of the
inverters set for system setting and the connected inverter are checked at parameter
batch write (refer to page 111 ) and All St. parameter setting (refer to page 103 ).
B
EEPROM write
When checked, parameter settings are written to both EEPROM and RAM regardless of
the Pr. 342 Communication EEPROM write selection setting.
When unchecked, parameter settings are written according to the Pr. 342 Communication
EEPROM write selection setting.
C
Release Test Operation
When checked, clicking or button of the test operation window once keeps the
motor running.
Note
• When test operation is being performed, check button of "Release Test Operation" cannot be checked.
• Setting of "R
elease Test Operation" and "EEPROM write" is not stored. At a start of FR Configurator, this setting is
always return to unchecked.
CAUTION
When communication stops (due to cable disconnection, etc.) after the test operation has been cancelled, the
inverter cannot be stopped from the personal computer.
Activate signal loss detection (Pr. 122, Pr. 336, or Pr. 548) or install an external stop device to always ensure the
safety.