Details of Setting Wizard
3
SETTING WIZARD
3.2.3 Analog input terminal calibration
Select "Analog Input Terminal Calibration" from "Setting Wizard"(Refer to page 105) in System View to start "Analog Input
Terminal Calibration". Terminal 2 and terminal 4 are calibrated.
(1) Setting flow
手動
Starting "Analog Input Terminal Calibration" wizard
Calibration method
Parameter List
Finish
Calibration without input
to the terminal
Calibration with input to the
terminal (ONLINE)
Calibration
frequency only
Calibrating Terminal and
Method
Calibration with input
to the terminal
Calibration without
input to the
terminal
Calibration only
frequency
Select the terminal to be calibrated and
calibration method.
Adjusting any point by application of
voltage (current) to the terminal and set
the frequency at that time. Click " "
to write the calibration value.
When calibrating both gain and bias,
calibrate bias first, and then calibrate gain.
Setting is available only when ONLINE.
Adjusting any point by application of
voltage (current) to the terminal and set
the frequency at that time.
Adjusting frequency without adjusting
voltage (current).