Instruction manual
26
Connection and Parameter Setting
*1 When "1" (Modbus-RTU protocol) is set in Pr. 549, the setting range within parentheses is applied.
*2 Pr. 551 is always write-enabled.
*3 Available for FR-A700, A701, F700 and F700P.
*4 Available for FR-A700, A701 and E700(SC).
*5 Available for FR-D700, E700(SC) and F700PJ.
*6 Available for FR-A700, D700, E700(SC) and F700PJ.
(2) Communication setting of GOT
If the communication setting of GOT is changed from the initial value, set the inverter communication setting to the same
as the GOT setting
341
*3
RS-485
communication CR/
LF selection
10, 1, 2
Select presence/absence of CR/LF.
(same specifications as Pr. 124)
551 *2
PU mode operation
command source
selection
FR-A701, F700,
F700P : 2
FR-A700, D700,
E700(SC),
F700PJ: 9999
1
*3
Selects the RS-485 terminal as the PU operation mode
command source.
2
Selects the PU connector as the PU operation mode
command source.
3
*4
Selects the USB connector as the PU operation mode
command source.
4
*5
Selects the operation panel as the PU operation mode
command source.
9999
*6
FR-A700: USB automatic recognition
Normally, operation panel (PU connector) is the command
source. During USB connection, USB is the command
source.
FR-D700, F700PJ : Parameter unit automatic recognition
FR-E700(SC): USB automatic recognition
During USB connection, USB is the command source.
Normally, operation panel is the command source. When the
parameter unit is connected to the PU connector, PU is the
command source.
Note
• Always reset the inverter after making the setting of the parameters. After you have changed the communication
related parameters, communication is not established until the inverter reset.
Item Description Initial value Range
Compatible
parameters
Transmission
Speed
Set this item to change the transmission speed used for
communication with the connected equipment.
19200bps
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
Pr. 118, Pr. 332
Data Bit
Set this item to change the data length used for communication with
the connected equipment.
7 bits 7bits/8bits
Pr. 119, Pr. 333
Stop Bit Specify the stop bit length for communications. 1 bit 1bit/2bits
Parity
Specify whether or not to perform a parity check, and how it is
performed during communication.
Odd
None
Even
Odd
Pr. 120, Pr. 334
Retry
Set the number of retries to be performed when a communication
timeout occurs.
0 time 0 to 5 times Pr. 121, Pr. 335
Timeout Time Set the time period for a communication to time out. 3s 1 to 30s -
Delay Time
Set this item to adjust the transmission timing of the communication
request from the GOT.
10ms 0 to 300ms -
Parameter
Num
be
r
Name Initial Value
Setting
Range
Description