OUTLINE
Connection and Parameter Setting
ยท Related parameter list
Parameter
Num
be
r
Name Initial Value
Setting
Range
Description
117
PU communication
station number
0
0 to 31
(0 to 247)
*1
Inverter station number specification
Set the inverter station numbers when two or more inverters
are connected to one personal computer.
118
PU communication
speed
192
48, 96, 192,
384
Set the communication speed.
The setting value x 100 equals the communication speed.
For example, the communication speed is 19200bps when
the setting value is "192".
119
PU communication
stop bit length
1
0
Stop bit length Data length
1 bit
8 bits
12 bits
10 1 bit
7 bits
11 2 bits
120
PU communication
parity check
2
0 Without parity check
1 With odd parity check
2 With even parity check
121
Number of PU
communication
retries
1
0 to 10
Set the permissible number of retries at occurrence of a data
receive error. If the number of consecutive errors exceeds the
permissible value, the inverter trips.
9999 If a communication error occurs, the inverter will not trip.
122
PU communication
check time interval
FR-A700, A701,
F700,
F700P : 9999
FR-D700,
E700(SC),
F700PJ : 0
0
RS-485 communication is enabled. Note that a
communication fault (E.PUE) occurs as soon as the inverter
is switched to the operation mode with control source.
0.1 to
999.8s
Communication check (signal loss detection) time interval
If a no-communication state persists for longer than the
permissible time, the inverter trips (depends on Pr. 502 ).
9999 No communication check (signal loss detection).
123
PU communication
waiting time setting
9999
0 to 150ms
Set the waiting time between data transmission to the inverter
and response.
9999 Set with communication data.
124
PU communication
CR/LF selection
1
0 Without CR/LF
1With CR
2With CR/LF
331 *3
RS-485
communication
station number
0
0 to 31
(0 to 247)
*1
Set the inverter station number.
Set the inverter station numbers when two or more inverters
are connected to one personal computer.
332 *3
RS-485
communication
speed
96
3, 6, 12, 24,
48, 96, 192,
384
Select the communication speed.
(same specifications as Pr. 118 )
333 *3
RS-485
communication
stop bit length
1 0, 1, 10, 11
Select stop bit length and data length.
(same specifications as Pr. 119)
334 *3
RS-485
communication
parity check
selection
2 0, 1, 2
Select the parity check specifications.
(same specifications as Pr. 120)
335 *3
RS-485
communication
retry count
1
0 to 10,
9999
Set the permissible number of retries at occurrence of a data
receive error.
(same specifications as Pr. 121)
336 *3
RS-485
communication
check time interval
0s
0
RS-485 communication is enabled. However, the inverter
trips if operation is changed to NET operation mode.
0.1 to
999.8s
Set the interval of communication check (signal loss
detection) time. (same specifications as Pr. 122)
9999 No communication check (signal loss detection)
337 *3
RS-485
communication
waiting time setting
9999
0 to 150ms,
9999
Set the waiting time between data transmission to the inverter
and response. (same specifications as Pr. 123)