Instruction manual
24
Connection and Parameter Setting
(1) Related parameter for connection of multiple inverters through GOT
Check a connection between the inverter and GOT, and set the following communication parameter when connecting
through GOT.
When performing parameter writing or run command input, set the following command source parameters, and switch
the operation mode to the following operation mode.
*1 Depending on the production year and month of FR-A700, the setting range and initial value of Pr. 551 may differ. For the details, refer to the Appendices of the
Instruction Manual of the inverter.
*2 FR-E700-SC/NC are not compatible with FR-E7TR.
Inverter
Communication Port
Parameter Setting
Operation
Mode
Communication Parameter
Command Source
Parameter
FR-A700,
A701,
F700,
F700P
PU connector
Pr. 119 PU communication stop bit length = "10"
(initial value 1)
Pr. 120 PU communication parity check = "1"
(initial value 2)
Pr. 121 Number of PU communication retries = "9999"
(initial value 1)
Pr. 122 PU communication check time interval
"0"
(initial value 9999)
Pr. 123 PU communication waiting time setting = "0"
(initial value 9999)
Initial value PU
RS-485 terminals
(Without communication
option)
Set the station number of the each inverter in Pr. 331
RS-485 communication station number (when connecting
multiple inverters)
Pr. 332 RS-485 communication speed = "192"
(initial value 96)
Pr. 333 RS-485 communication stop bit length = "10"
(initial value 1)
Pr. 334 RS-485 communication parity check selection =
"1"
(initial value 2)
Pr. 335 RS-485 communication retry count = "9999"
(initial value 1)
Pr. 336 RS-485 communication check time interval
"0"
(initial value 0)
Pr. 337 RS-485 communication waiting time setting = "0"
(initial value 9999)
Initial value NET
RS-485 terminals
(With communication
option)
Pr. 551 PU mode operation
command source selection = "1"
(initial value 9999: FR-A700)
*1
(initial value 2: FR-A701,
F700 and F700P)
PU
FR-
E700(SC)
PU connector
(Without communication
option)
Set the station number of the each inverter in Pr. 117
PU communication station number (when connecting
multiple inverters)
Pr. 119 PU communication stop bit length = "10"
(initial value 1)
Pr. 120 PU communication parity check = "1"
(initial value 2)
Pr. 121 Number of PU communication retries = "9999"
(initial value 1)
Pr. 122 PU communication check time interval
"0"
(initial value 0)
Pr. 123 PU communication waiting time setting = "0"
(initial value 9999)
Initial value NET
PU connector
(With communication
option)
Pr. 551 PU mode operation
command source selection = "2"
(initial value 9999)
PU
RS-485 terminal option
*2
(Without communication
option)
Initial value NET
RS-485 terminal option
*2
(With communication
option)
Pr. 551 PU mode operation
command source selection = "2"
(initial value 9999)
PU
FR-D700,
F700PJ
PU connector Initial value NET
REMARKS
· Switching of the operation mode is available at "Test Operation" window (Refer to page 97) in Navigation area.
· Set the station number of the each inverter in Pr. 117 PU communication station number, Pr.331 RS-485 communication station
number when connecting multiple inverters. Perform inverter reset after setting the parameter.