Error Code
5.1.2 Communication error when connected through GOT
POINT
If a Time Out error occurs, set FR Configurator to OFFLINE. Please check a communication cable connection etc, to fix the error
and then set FR Configurator to ONLINE again.
Error Code
HEX)
Error Message Cause Countermeasure
0x80110001
An unexpected error
occurred to S/W.
GOT type error. Check for the GOT type.
0x80110002
0x80110003
An unexpected error
occurred to S/W.
Please contact your sales representative.
0x80110004
Failed to make a
communication with the
inverter during the time set
with Time Out.
1. Communication protocol of the inverter
and GOT are not the same.
2. Setting of Pr. 122 PU communication check
time interval, Pr. 336 RS-485
communication check time interval, Pr. 548
USB communication check time interval is
other than "0".
3. Electromagnetic interference
4. Cable breakage/damaged
1. Set communication protocol of the
inverter and GOT same.
2. Set a value other than "0" in Pr. 122 PU
communication check time interval, Pr. 336
RS-485 communication check time interval,
Pr. 548 USB communication check time
interval .
3. Set larger value for Time Out setting of
the software.
4. Cable connection/replacement
Check for communication cable and
power supply of devices.
0x80110005
Failed to make a
communication with the
inverter during the time set
with Time Out.
FR Configurator was started and a
communication was established when GX
drawing software was starting.
After closing GX drawing software, try
communication again.
0x80110006
Failed to make a
communication with the
inverter during the time set
with Time Out.
GX drawing software was started when FR
Configurator was starting.
After closing GX drawing software, try
communication again.
0x80110007
An unexpected error
occurred to S/W.
Communication line quality error
Set lower baud rate and make a
communication.
0x80110008
An unexpected error
occurred to S/W.
Baud rate not supported by connected
device
Check for the baud rate supported by
connected devices.
0x80110009
Failed to make a
communication with the
inverter during the time set
with Time Out.
1. Electromagnetic interference
2. Cable breakage/damage
1. Set larger value for Time Out setting of
the software.
2. Cable connection/replacement
Check that line is connected.
0x8011000A
Failed to make a
communication with the
inverter during the time set
with Time Out.
Other process is ongoing in GOT and line is
BUSY.
(retry is performed in the EZSocket)
A station not connected is being monitored.
Set a larger value for Time Out setting of
the software.
Monitor only the station which the GOT is
connected.
Check that the GOT is operating correctly
and try again.
0x8011000B
An unexpected error
occurred to S/W.
Protocol type error Check for protocol type.
0x8011000C
An unexpected error
occurred to S/W.
Host name error Check for connected GOT host name.
0x8011000D
An unexpected error
occurred to S/W.
Socket port number error Check for the port number.