166
Error Code
0x80010014
Parameter writing to a write
disabled parameter is
unavailable.
1. Writing is disabled by Pr. 77 Parameter
write selection.
Pr. 77 = 1 (write disabled)
2. Password lock is activated.
1. Change the setting of Pr. 77 Parameter
write selection except for "1".
2. Enter the password in Pr. 297 to unlock
the password lock.
0x80010016
Can not read/write an
nonexistent parameter.
1. Version of inverter and version of setup
software parameter file is not
corresponding.
2. Simple mode is set by Pr. 160 User group
read selection.
3. Password lock is activated.
1. Reinstallation of the software
2. Change the setting of Pr. 160 except for
simple mode setting.
3. Enter the password in Pr. 297 to unlock
the password lock.
0x80010017
Specified option is not
installed in the inverter.
Reading of option parameter was attempted
while the option is not installed.
Install the option to the inverter.
0x80010018
There is no difference
between the analog setting
of gain and bias.
There is only small difference between the
analog setting of gain and bias.
Set larger setting between the analog
setting of gain and bias.
0x8001001A
Unsupported model is
connected.
If FR-E500 is connected to the station where FR-E700 is set for system setting, switching
to ONLINE will display a communication error dialog. In this case, click OK, and proceed
converting.
If the case is not the one above, please contact your sales representative.
0x80010021
Operation mode switching
during inverter operation is
unavailable.
Change the operation mode after the
inverter stop.
Set "2" in Pr. 77 Parameter write selection.
Stop the inverter.
0x80010022
When forward rotation
signal (STF) is ON,
switching to External mode
is unavailable.
Switching to External mode was attempted
when forward rotation signal (STF) is ON.
Change the operation mode after switching
STF to OFF.
0x80010023
When reverse rotation
signal (STR) is ON,
switching to External mode
is unavailable.
Switching to External mode was attempted
when reverse rotation signal (STR) is ON.
Change the operation mode after switching
STR to OFF.
0x80010024
Switching of operation
mode is unavailable with
current operation mode.
Attempted to switch the operation mode
other than the one set in Pr. 79 Operation
mode selection.
Change the setting of Pr. 79 Operation mode
selection.
0x80010025
Reset is unavailable with
current setting.
Reset is restricted by P
r. 75 Reset selection/
disconnected PU detection/PU stop selection.
Change the setting of Pr. 75 Reset selection/
disconnected PU detection/PU stop selection.
0x80010026
An unexpected error
occurred to S/W.
Please contact your sales representative.
0x80010101
Failed to make
communication with the
inverter during the time set
with Time Out.
1. Setting of Pr. 122 PU communication check
time interval , Pr. 336 RS-485
communication check time interval, Pr. 548
USB communication check time interval is
too small.
2. Electromagnetic interference
3. Cable breakage/damage
4. Personal computer port is set invalid/
port breakage
1. Set larger value or 9999 in Pr. 122 PU
communication check time interval, Pr. 336
RS-485 communication check time interval,
Pr. 548 USB communication check time
interval.
2. Set larger value for Time Out setting of
the software.
3. Cable connection/replacement
4. Activate the port by using Device
Manager/port replacement
0x80010102
Illegal data is included in
the data received by the
computer.
1. Setting of Pr. 124 PU communication CR/
LF selection, Pr. 341 RS-485
communication CR/LF selection is
different with software setting.
2. Electromagnetic interference
3. Inverter reset (or power-OFF)
4. Cable breakage
1. Set Pr. 124 PU communication CR/LF
selection, Pr. 341 RS-485 communication
CR/LF selection same as the setting of
the software.
2. Set larger value in Pr. 121 Number of PU
communication retries, Pr. 335 RS-485
communication retry count.
3. Do not reset the inverter or turn OFF the
inverter power during communication.
4. Replacement of cable
Error Code