Instruction manual
165
Error Code
5
TROUBLE INDICATION
0x80010004
The stop bit length differs
from the initial setting.
1. Setting of Pr. 119 PU communication stop
bit length, Pr. 333 RS-485 communication
stop bit length is different with software
setting.
2. Electromagnetic interference
3. Cable breakage
1. Set Pr. 119 PU communication stop bit
length, Pr. 333 RS-485 communication stop
bit length same as the setting of the
software.
2. Set larger value in Pr. 121 Number of PU
communication retries, Pr. 335 RS-485
communication retry count.
3. Replacement of the cable
0x80010005
Due to wiring error, next
data intruded before data
reception is completed.
1. Setting of Pr. 123 PU communication
waiting time setting, Pr. 337 RS-485
communication waiting time setting is too
small.
2. Electromagnetic interference
3. Cable breakage
1. Set larger value or 9999 in Pr. 123 PU
communication waiting time setting, Pr.337
RS-485 communication waiting time
setting.
2. Set larger value in Pr. 121 Number of PU
communication retries, Pr. 335 RS-485
communication retry count.
3. Replacement of the cable
0x80010007
The character received is
invalid (other than 0 to 9, A
to F, control code).
1. Setting of Pr. 119 PU communication stop
bit length, Pr. 333 RS-485 communication
stop bit length is different with software
setting.
2. Electromagnetic interference
3. Cable breakage
1. Set Pr. 119 PU communication stop bit
length, Pr. 333 RS-485 communication stop
bit length same as the setting of the
software.
2. Set larger value in Pr. 121 Number of PU
communication retries, Pr. 335 RS-485
communication retry count.
3. Replacement of the cable
0x8001000A A mode error occurred.
Parameter setting or frequency setting was
performed in the operation mode such as
External operation (EXT) etc. which has no
parameter setting and speed command
source with FR Configurator.
Change the operation mode to the PU
operation mode (or NET).
Check the setting value of Pr. 338
Communication operation command source, Pr.
550 NET mode operation command source
selection, Pr. 551 PU mode operation command
source selection.
(Operation command source changes
according to inverter communication
connection. Refer to page 12, 27)
0x8001000C
An unexpected error
occurred to S/W.
Please contact your sales representative.
0x80010011
You cannot write a value
out of range to parameter.
Tried to write a value out of setting range of
the parameter.
Set a value within the setting range, and
write.
If a writing error occurs even if a value is
written within the setting range, check for
writing requirements of each parameter.
Refer to the Instruction Manual of the inverter
for w
riting requirements.
0x80010012 A mode error occurred.
1. Pr. 79 Operation mode selection is not set
for PU/NET (RS-485).
2. Parameter setting or frequency setting
was performed in the operation mode
such as External operation (EXT) etc.
which has no parameter setting and
speed command source with FR
Configurator.
1. Click [PU] button of Test Operation.
Change the setting of Pr. 79 for PU/
NET (RS-485).
2. Change the operation mode to the PU
operation mode (or NET).
Check the setting value of Pr. 339
Communication speed command source, Pr.
551 PU mode operation command source
selection. (Speed command source
changes according to inverter
communication connection. Refer to
page 12, 27
0x80010013
Parameter writing during
inverter operation is
unavailable.
Parameter writing was attempted during
inverter operation.
Perform parameter writing after inverter is
stopped.
Error Code
(HEX)
Error Message Cause Countermeasure