Instruction manual

164
Error Code
5.1 Error Code
If a communication error is detected, the following communication error code and error message appears in the
communication error dialog (Refer to page 36).
5.1.1 Communication error with the inverter
POINT
If a Time Out error occurs, set FR Configurator to OFFLINE. Please check a communication cable connection, etc. to fix the error
and then set FR Configurator to ONLINE again.
Error Code
(HEX)
Error Message Cause Countermeasure
0x01010001
Failed to write because the
parameter writing
destination was not
successfully changed to
EEPROM. ( )
Failed to write Pr. 342 at batch parameter
writing.
Refer to the error code displayed in ( ) of
the message, and enable the writing of Pr.
342.
0x80A00101
Failed to open a
communication line.
1. Communication setting is not set for
USB while connecting with USB.
2. No communication port existed on the
personal computer. Or not recognized.
1. Check for connection configuration at
[O
ptions] in [Tool] menu. (Refer to page
91)
2. Check that communication port exists
on the personal computer.
0x80A00104
0x80A00107
0x80A0010A
An unexpected error
occurred to S/W.
Please contact your sales representative.
0x80010000
Errors from computer in a
row are more than the retry
count.
1. Setting of Pr. 124 PU communication CR/
LF selection, Pr. 341 RS-485
communication CR/LF selection is
different with software setting.
2. Electromagnetic interference
3. Cable breakage
1. Set Pr. 124 PU communication CR/LF
selection, Pr. 341 RS-485 communication
CR/LF selection same as the setting of
the software.
2. Set larger value in Pr. 121 Number of PU
communication retries, Pr. 335 RS-485
communication retry count.
3. Replacement of the cable
0x80010001
The parity check result
does not match the
specified parity.
1. Setting of Pr. 120 PU communication
parity check, Pr. 334 RS-485
communication parity check selection is
different with software setting.
2. Electromagnetic interference
3. Cable breakage
1. Set Pr. 120 PU communication parity
check, Pr. 334 RS-485 communication
parity check selection same as the setting
of the software.
2. Set larger value in Pr. 121 Number of PU
communication retries, Pr. 335 RS-485
communication retry count.
3. Replacement of the cable
0x80010002
The sum check code in the
computer does not match
that of the data received by
the inverter.
1. Communication setting is different
between the inverter and the software.
2. Data is corrupted due to
electromagnetic interference, etc.
1. Make a same communication setting.
2. Check for electromagnetic interference
and wiring.
0x80010003
Data received by the
inverter is in the wrong
protocol, or data receive is
not completed within the
given time.
1. Setting of Pr. 124 PU communication CR/
LF selection, Pr. 341 RS-485
communication CR/LF selection is
different with software setting.
2. Electromagnetic interference
3. Cable breakage
1. Set Pr. 124 PU communication CR/LF
selection, Pr. 341 RS-485 communication
CR/LF selection same as the setting of
the software.
2. Set larger value in Pr. 121 Number of PU
communication retries, Pr. 335 RS-485
communication retry count.
3. Replacement of the cable