I/O Terminal Monitor (Monitor Area)
4
FUNCTION
4.11 I/O Terminal Monitor (Monitor Area)
You can check terminal assignment status of I/O terminal of the inverter, and plug-in option (FR-A7AR, FR-A7AX, FR-A7AY),
and ON/OFF state of each terminal. The monitor turns green when terminal is ON and turns black when terminal is OFF. You
can also start Wizard (Refer to page 154) for function assignment of each I/O terminal from "I/O Terminal Monitor".
Select [I
/O Terminal Monitor] in [View] menu to display "I/O Terminal Monitor".
No. Name Function and Description
A
Start Starts monitoring of I/O terminal.
B
Stop Stops monitoring of I/O terminal. (I/O terminal state is held at the monitor stop.
C
Clear Clears signal status (ON/OFF state) of I/O terminal.
D
Assign
Starts I/O terminal assignment wizard (Refer to page 154). I/O terminal can be assigned when ONLINE
and during not monitoring.
E
Station number Displays the station number of the monitoring inverter.
F
Monitor status
Shows a state of monitor. If an error occurs, the color changes to red to indicate an error stop. During
monitoring, the following indication appears to indicate monitoring.
G
Inverter input terminal state Displays input terminal state and function assignment status of the inverter.
H
Inverter output terminal
state
Displays output terminal state and function assignment status of the inverter. If negative logic is set,
"(negative logic)" is displayed after function name.
I
Option input terminal state
Displays input terminal state of the plug-in option (FR-A7AX), function assignment status, and
numerical data of the terminal. Displays numerical data of the terminal in hexadecimal and decimal in
parentheses.
J
Option output terminal state
Displays output terminal state and function assignment status of the plug-in option (FR-A7AR and
FR-A7AY). If negative logic is set, "(Negative Logic)" is displayed after function name.
FBA EC
H
G
I
J
D