Instruction manual

150
Graph (Monitor Area)
When sampling with Fault trigger, starting at a fault occurrence, with 90% of sampling data before the
fault occurrence
(1) Select "00" at St. No. field.
Select "Output Frequency" at Name field in CH1,
"RUN" in CH5, and "FU" in CH6.
(2) Make trigger setting as follows:
Select "Fault" at Type field.
Select "00" at St. No. field.
Input "90" at Position [%] field.
Set sampling interval and sampling time.
(3) Click to show "Sampling Pre-trigger
Data", and retrieves the data before the trigger
meets condition.
After the retrieval of the data before the trigger
meets condition, then the screen shows "Waiting
for Trigger" and becomes the trigger waiting state.
(4) When inverter fault occurs, sampling starts
automatically.
(5) Click , or the sampling time has passed,
and then the sampling is finished.
(6) Graph is adjustable for a better viewing.
(7) Graph data can be exported (Refer to page 94) for saving data as a file.
REMARKS
In this example, "Position [%]" is set to "90%". The fault occurrence during the 90% of the sampling time after clicking
(during Pre-Trigger state) is ignored, and sampling is not started.