Instruction manual

132
Convert (System Area)
<When converting the FR-F500J series to the FR-F700PJ series >
( ) indicates parameter number for the FR-F500J series.
(1) The following parameters are not converted. Make a setting from "Parameter List" as required.
Pr. 133 PID action set point
Pr. 160 (P30) Extended function display selection
Pr. 900, Pr. 901 (FM, AM output terminal calibration)
Pr. 991 PU contrast adjustment
(2) The following parameters are adjustment parameters. Parameter readjustment according to the machine is
recommended after converting.
Pr. 0 Torque boost
Pr. 12 DC injection brake operation voltage
Pr. 245 (P95) Rated slip
Pr. 246 (P96) Slip compensation time constant
Pr. 902 to 905, 922, 923 (C3, C4, C6, C7) (frequency setting input calibration parameter)
(3) When Automatic torque boost is selected (Pr.98 Motor capacity is not "9999") for the FR-F500J series, note the following
precautions.
Tuning and parameter setting of the target inverter are recommended.
When SF-HR or SF-HRCA type motor is used, set Pr.71 = "40, 43, 50, 53" after writing the converted parameters to the
target inverter.
(4) Communication related parameters (Pr.117 to Pr.124 (n1 to n7, n11)) are also converted. Depending on a setting,
communication may not be established after writing the parameters. For example, if Pr.122 (n6) PU communication check
time interval = "0" (initial value), changing to the command source operation mode causes a communication fault
(E.PUE).
(5) The following functions have different behavior due to specification changes. Refer to the Instruction Manual of FR-
F700PJ for details.
Since the formula of Pr.23 Stall prevention operation level compensation factor at double speed has been changed, the
operation level of the stall prevention at double speed changes if the setting has been changed greatly from 100%.
Pr.992 (n16) PU main display screen data selection is integrated into Pr.52 . Setting Pr.52 changes both operation panel
display and PU display.
(6) The following function is not converted since it has been deleted from the FR-F700PJ series.
Pr.93 PID action set point for PU operation