Convert (System Area)
4
FUNCTION
<When converting the FR-F500 (L) series to the FR-F700 or FR-F700P series >
(1) Since the following parameters are not converted, make a setting from "Parameter List" as required.
• Pr. 133 PID action set point
• Pr. 160, Pr. 173 to Pr. 176 (User group selection)
• Pr. 900, Pr. 901 (FM, AM output terminal calibration)
• Pr. 991 PU contrast adjustment
(2) The following parameters are adjustment parameters. Parameter readjustment according to the machine is
recommended after converting.
• Pr. 0 Torque boost
• Pr. 12 DC injection brake voltage
• Pr. 902 to Pr. 905 (frequency setting input calibration parameter)
(3) Automatic torque boost (Pr.38, Pr.39) of the FR-F500(L) series has been changed to Simple magnetic flux vector control
for the FR-F700 and FR-F700P series. When automatic torque boost is used and operation conditions meets Simple
magnetic flux vector control, then manually set Simple magnetic flux vector control. Refer to the Instruction Manuals of
the FR-F700 and FR-F700P series.
(4) Communication related parameters (Pr. 117 to Pr. 124, Pr. 331 to Pr. 337, 341) are also converted. Depending on a setting,
communication may not be established after writing the parameter. For example, if Pr. 122 or Pr. 336 Communication check
time interval = "0" (initial value), changing to the command source operation mode causes a communication fault (E.PUE
or E.SER).
(5) The following wiring needs to be changed. For the details of wiring methods, refer to the Instruction Manuals of the FR-
F700 and FR-F700P series.
• When a relay output terminal of the FR-A5NR was used, change the connection to terminal ABC2 of the inverter.
(6) There is a change in the following functions. Refer to the Instruction Manuals of the FR-F700 and FR-F700P series.
• Since formula of Pr. 23 Stall prevention operation level compensation factor at double speed has been changed, operation
level of stall prevention at double speed changes if the setting has been changed greatly from 100%.
• When using CC-Link communication with the FR-A5NC, set the communication station number and baud rate in Pr.
542 and Pr. 543 according to the rotary switch setting of the FR-A5NC.
(7) The following functions are not convertible because they have been deleted or changed in the FR-F700 and FR-F700P
series.
• Pr. 11 setting 8888 (external DC injection brake)
• Pr. 38 Automatic torque boost
• Pr. 39 Automatic torque boost operation starting current
• Pr. 53 PU level display data selection
• Setting 3 of Pr. 60, Pr. 61 to Pr. 63 (optimum acceleration/deceleration)
• Pr. 93 PID action set point for PU operation
• Pr. 199 User initial value
• Pr. 390 to Pr. 396 Trace function of the FR-F500L series
• Pr. 508 Output stop cancel process value level