Instruction manual
127
Convert (System Area)
4
FUNCTION
<When converting the FR-E500 series to the FR-D700 series >
(1) The following parameters are not converted. Make a setting from "Parameter List" as required.
• Pr. 133 PID action set point
• Pr. 146 Frequency setting command selection
• Pr. 900, Pr. 901 (FM, AM output terminal calibration)
• Pr. 991 PU contrast adjustment
(2) The following parameters are adjustment parameters. Parameter readjustment according to the machine is
recommended after converting.
• Pr. 0 Torque boost
• Pr. 12 DC injection brake voltage
• Pr. 245 Rated slip
• Pr. 246 Slip compensation time constant
• Pr. 902 to 905, 922, 923 (frequency setting input calibration parameter) *
* Depending on a product date of FR-E500, converting of Pr. 902, 903, 922 and 923 may not be available. In this case, please adjust the parameter
setting manually after the convert.
(3) When General-purpose magnetic-flux vector control is selected ( Pr. 80 Motor capacity is not "9999") for FR-E500 series,
note the following precautions.
• Tuning and parameter setting of the target inverter are recommended, if offline auto tuning is performed ( Pr. 71 Applied
motor = "3, 13, 23, 103, 113, 123”) or motor constants is directly input ( Pr. 71 = "5, 6, 15, 16, 105, 106, 115, 116") to the
source inverter.
• When SF-HR or SF-HRCA type motor is used, set Pr. 71 = "40, 43, 44, 50, 53, 54" after writing the converted
parameter to the target inverter. (Conversion of Pr. 82, Pr. 86, Pr. 90 is not necessary)
(4) Communication related parameters (Pr. 117 to Pr. 124) are also converted. Depending on a setting, communication may
not be established after writing the parameter. For example, if Pr. 122 PU communication check time interval = "0" (initial
value), changing to the command source operation mode causes a communication fault (E.PUE).
(5) When communication operation is selected with the FR-E500 series, parameter writing and operation command
sending, etc. is performed in PU operation mode. Therefore, one of the following setting is required for FR-D700 series.
•Set Pr. 79 = "1"(PU operation mode always), Pr. 551 = "2"(PU control source is PU connector), and change to PU
operation mode. Note that parameter writing and operation command from the operation panel is unavailable.
•Set Pr. 79 = "0"(initial value), Pr. 340 = "1" (Network operation mode at power-ON), and change to Network operation
mode.
(6) If FR-E510W or FR-E520S is connected and convert from the connected inverter through communication is performed,
the inverter is detected as FR-E520. Check that a compatible inverter is connected for source inverter, and then perform
inverter detection.
(7) Since FR-D700 series does not have Pr. 21 (Acceleration/deceleration time increments), if Pr. 21 = "1", the setting value of
the hundredth place of the following parameters are rounded to the tenth place.
(8) The following functions are not converted, since they have been deleted or changed from the FR-D700 series.
• Pr. 21 Acceleration/deceleration time increments
• Pr. 38 Frequency at 5V (10V) input
• Pr. 39 Frequency at 20mA input
• Pr. 60 Shortest acceleration/deceleration mode
• Pr. 61 Reference current
• Pr. 62 Reference current for acceleration
• Pr. 63 Reference current for deceleration
• Pr. 183 MRS terminal function selection
• Pr. 191 FU terminal function selection
• Pr. 160, 173 to 176 (User group selection)
• Pr. 345 to 348 (DeviceNet communication)
• Pr. 387 to 392 (LonWorks communication)
• Pr. 500, 501 (communication option parameter)