Specifications

External Connection Diagram External Dimension Diagram
75
Operating condition LED display
Connector for communication
Connector for analog I/O
Connector for power supply
For a detailed description of the connectors, see page 108.
SELECT/SET switch
For wire, use two-core shielded twisted-pair cable.
Indicate the input resistance of AJ65VBTCU-68ADI.
Connect a capacitor of around 0.1 to 0.47 µF (it must be a product that
can withstand voltages of 25 V or more) between the V and COM termi-
nals if noise or ripple is generated in the external wiring.
Be sure to ground FG1. There are cases where AG should also be
grounded if the signal is particularly noisy.
The offset or gain value should be set again if the ground wiring is
changed after setting the offset or gain value (whether the signals were
connected to ground or not).
1
2
3
4
LED display for offset/gain adjustment
Unit: mm
Description
POWER
RUN
L RUN
L ERR.
On: When the power supply is turned
Normal mode
Test mode
On: When the communication is normal
Off: When the communication is normal
On: Normal operation
On: When the SELECT/SET
switch is in the SET position
Off: When the SELECT/SET
switch is in the SELECT
or central position
Pin no.
Name
4
SLD
3
NC
2
V/I
1
V/I
Pin no.
Name
5
SLD
4
NC
3
DG
2
DB
1
DA
3
2
4
1 Shield
1 Shield
AJ65VBTCU-68ADVN (in case of voltage input)
AJ65VBTCU-68ADVN (in case of current input)
Signal source: 0 to 10V
Signal source 0 to 20mA
CH1
CH8
500k
500k
500k
250k
500k
+15V
-15V
GND
GND
1
2
3
4
V+
V-
NC
SLD
1
2
3
4
I+
I-
NC
SLD
AG
FG1
Connector pin no.
Connector pin no.
54321
Pin no.
Name
5
FGI
4
AG
3
Module 24V
2
Module 24V
1
FG
Connector pin no.
54321
4321
Name and Setting of Each Part
Analog Modules AJ65VBTCU-68ADVN AJ65VBTCU-68ADIN
Rated plate
Product
Description
Master/Local
Remote I/OAnalog
High-Speed
Counters
PositioningHMIRepeatersRS-232
Interfaces
OptionSoftwareOthers
Technical
Information
CC-Link
-
CC-Link / LT
Bridge Modules
Support PC
Interfaces
Peripheral
Device
Connection
Mode selector switch
Station number setting switch
Transmission speed setting switch
Description
 
0: Normal mode
1: Test mode
(user range setting 1)
2: Test mode
(user range setting 2)
3: Normal mode
4: Test mode
(user range setting 1)
5: Test mode
(user range setting 2)
6 to 7: Not used
 
0: Normal mode
1: Test mode
(user range setting 1)
3: Normal mode
4: Test mode
(user range setting 1)
257: Not used
 
"10," "20," and "40" in STATION NO. are used for setting
the second digit of the station number.
"1," "2," "4," and "8" in STATION NO. are used for setting
the first digit of the station number.









 