Specifications

153
Overview of CC-Link
With Ver. 2, the cyclic data size can be increased through extended cyclic setting.
Differences Between Versions 2 and 1
CC-Link Ver. 1 specification
Number of linked
points for each
occupied station
number
1station occupied
2station occupied
3station occupied
4station occupied
Number of connected modules
Item Specification
Remote I/0RXRY2048 points each
Remote I/0RXRY32 points each
Remote I/0RXRY32 points each
Remote I/0RXRY64 points each
Remote I/0RXRY96 points each
Remote I/0RXRY128 points each
Remote registerRWw256 words
Remote registerRWw4 words each
Remote registerRWw4 words each
Remote registerRWw8 words each
Remote registerRWw12 words each
Remote registerRWw16words each
Remote registerRWr256 words
Remote registerRWr4 words each
Remote registerRWr4 words each
Remote registerRWr8 words each
Remote registerRWr12 words each
Remote registerRWr16 words each
Total number of stations
(1×a)(2×b)(3×c)(4×d)≦64
a: Number of modules of 1 occupied station, b: Number of modules of 2 occupied stations,
c: Number of modules of 3 occupied stations, d: Number of modules of 4 occupied station
Number of connected modules
(16×A)(54×B)(88×C)≦2304
A: Number of modules of remote I/O station Max. 64 modules
B: Number of remote device stations Max. 42 modules
C: Local station, waiting master station, intelligent device station Max. 26 modules
CC-Link Ver. 2 specification
Maximum number of link points
Number of link
points per station
Remote I/0RXRY
Remote registerRWw
Remote registerRWr
1station
occupied
Number of Linked points for each
occupied station number
2station
occupied
3station
occupied
4station
occupied
Remote I/0RXRY
Remote registerRWw
Remote registerRWr
Remote I/0RXRY
Remote registerRWw
Remote registerRWr
Remote I/0RXRY
Remote registerRWw
Remote registerRWr
Remote I/0RXRY
Remote registerRWw
Remote registerRWr
Expanded cyclic setting
Number of connected modules
Single Double Quadruple Octuple
Item Specification
Remote I/0RXRY8192 points each, Remote registerRWw 2048points , Remote registerRWr2048points
Total number of stations
(a+a2+a4+a8)b+b2+b4+b8)×2(c+c2+c4+c8)×3(d+d2+d4+d8)×4≦64
Number of input/output points of all remote stations
(a×32+a2×32+a4×64+a8×128)(b×64+b2×96+b4×192+b8×384)
 +c×96+c2×160+c4×320+c8×640)(d×128+d2×224+d4×448+d8×896)≦8192
Number of all remote register words
(a×4+a2×8+a4×16+a8×32)(b×8+b2×16+b4×32+b8×64)
 +c×12+c2×24+c4×48+c8×96)(d×16+d2×32+d4×64+d8×128)≦2048
a Number of modules of single setting of 1 occupied station
c Number of modules of single setting of 3 occupied station
a2Number of modules of double setting of 1 occupied station
c2Number of modules of double setting of 3 occupied station
a4
Number of modules of quadruple setting of 1 occupied station
c4
Number of modules of quadruple setting of 3 occupied station
a8Number of modules of octuple setting of 1 occupied station
c8Number of modules of octuple setting of 3 occupied station
Number of connected modules
(16×A)(54×B)(88×C)≦2304
A: Number of modules of remote I/O station Max. 64 modules
B: Number of remote device stations Max. 42 modules
C: Local station, waiting master station, intelligent device station Max. 26 modules
b Number of modules of single setting of 2 occupied station
d Number of modules of single setting of 4 occupied station
b2Number of modules of double setting of 2 occupied station
d2Number of modules of double setting of 2 occupied station
b4
Number of modules of quadruple setting of 2 occupied station
d4
Number of modules of quadruple setting of 4 occupied station
b8Number of modules of octuple setting of 2 occupied station
d8Number of modules of octuple setting of 4 occupied station
32 points each
4 words
4 words
32 points each
8 words
8 words
64 points each
16 words
16 words
128 points each
32 words
32 words
32 points each
4 words
4 words
32 points each
8 words
8 words
64 points each
16 words
16 words
128 points each
32 words
32 words
64 points each
8 words
8 words
96 points each
16 words
16 words
192 points each
32 words
32 words
384 points each
64 words
64 words
96 points each
12 words
12 words
160 points each
24 words
24 words
320 points each
48 words
48 words
640 points each
96 words
96 words
128 points each
16 words
16 words
224 points each
32 words
32 words
448 points each
64 words
64 words
896 points each
128 words
128 words
Master/Local
Remote I/OAnalog
High-Speed
Counters
PositioningHMIRepeatersRS-232
Interfaces
OptionSoftwareOthers
Technical
Information
CC-Link
-
CC-Link / LT
Bridge Modules
Support PC
Interfaces
Peripheral
Device
Connection
*and are Ver. 2 mode only; calculation is necessary.
* There is no change in the cable and wiring specification for CC-Link Ver. 2. Use Ver. 1 cable for the connection of Ver. 2 devices. For details of cable wiring specification, refer to pages 152 and 154.
Maximum number of link points
Number of link points per station