Differences Between Versions 1.10 and 1.00
Specification List of CC-Link Version 1.00 (Differences from Version 1.10)
■The specifications of CC-Link Version 1.10 and Version 1.00 differ with respect to the following two subjects:
●Maximum total cable length and cable length between stations
●Connection cable
Maximum total cable length
and cable length between stations
Connection cable
156kbps
625kbps
2.5Mbps
5Mbps
10Mbps
Maximum total
cable length
1200m
600m
200m
110m
150m
50m
80m
100m
Cable length between stations
*1
30 cm min.
30 to 59 cm
60 cm min.
30 to 59 cm
60 to 99 cm
1 m min.
*2
1m
min.
/2m
min.
CC-Link dedicated cable (terminal resistor 110Ω is used)
Master station
Maximum total cable length
*2
*1 Cable length between remote I/O stations or remote device stations
*2 Cable length between the master/local station or intelligent device station and stations before and after
CC-Link dedicated cable/CC-Link dedicated high performance cable
・The dedicated cable and dedicated high performance cable cannot be used together.
・Cables from different manufacturers cannot be used together.
*1 *2 *2
Remote I/O
station or remote
device station
Remote I/O
station or remote
device station
Local station or
intelligent
device station
Local station or
intelligent
device station
1m or more in case of a system con-
figuration with remote I/O and re-
mote device stations only.
2m or more in case of a system con-
figuration that includes local stations
and intelligent device stations.
(A):
(B):
Item Specification
(A)
(B)
Technical Information
Overview of CC-Link
Communication
speed
If wiring is made with this range of the cable length between remote IO
stations or remote device stations in at least at one place, the maximum
total cable length above must be used.