Service manual
3
■ R-Converter Unit
PAC - SF 29 LB
(Indispensable)
Optional parts
of PAC
Symble of
factory
Lev Box
Design code No.
1-3. METHOD FOR IDENTIFYING
PUMY-P125YMA
MSH-18RV SLH-1.6AR MSC-09RV MSC-09RV MSC-07-RV
Living
R-Converter Unit
(PAC-SF29LB)
R-Converter Unit
(PAC-SF29LB)
R-Converter Unit
(PAC-SF29LB)
R-Converter Unit
(PAC-SF29LB)
R-Converter Unit
(PAC-SF29LB)
Bedroom (1) Bedroom (2) Bedroom (3)
Dining
■ Verification
The rated capacity should be determined by observing the below. The unit’s quantities are limited in 1 to 8 units. For
the next step, make sure that the selected total indoor unit capacity is in a range of 63 ~ 163.
The total indoor unit capacity should be within the outdoor units. (=125 is preferred).
Combination of excessive indoor units and an outdoor unit may reduce the cooling capacity of each indoor unit.
The rated indoor capacity is as blow table.
Example:
MSH-18 = 50
SLH-1.6 = 40
MSC-09 = 25
MSC-09 = 25
MSC-07 = 20
Total rated capacity
160 163
1-4. TYPICAL COMBINATION EXAMPLE
W Capacity type of indoor units
Refer to page 2.
OC296--1.qxp 03.6.11 9:36 AM Page 3