OB207t-1qxp 25/9/97 8:51 PM Page 1 This Servise Manual OB207 deals with MSH-07/09/12/18/24NV-E1, MUH-07/09/12/18/24NV-E1, MSH-18NV-E2, and MUH-18NV-E2 in OB176 REVISED EDITION-A issued in July in1997. Therefore, please refer to OB207, not to OB176 REVISED EDITION-A, for the above models. SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS No.
OB207t-1qxp 1 25/9/97 8:51 PM Page 2 TECHNICAL CHANGES MSH-17NV - E1 ➔MSH-07NV - E2 1. Indoor electronic control P.C.board has changed. However, it is compatible between E1 and E2 models. 2. Auto restart function is added. MSH-09NV - E1 ➔MSH-09NV - E2 1. Indoor electronic control P.C.board has changed. However, it is compatible between E1 and E2 models. 2. Auto restart function is added. MSH-12NV - E1 ➔MSH-12NV - E2 1. Indoor electronic control P.C.board has changed.
OB207t-1qxp 25/9/97 8:51 PM 2 Page 3 PART NAMES AND FUNCTIONS INDOOR UNIT MSH-07NV - E2 MSH-09NV - E2 MSH-12NV - E2 MSH-07NV - E1 MSH-09NV - E1 MSH-12NV - E1 (When the front panel is open) MSH-07NV - E1 MSH-09NV - E1 MSH-07NV - E2 MSH-09NV - E2 MSH-18NV - E1 MSH-24NV - E2 MSH-24NV - E1 MSH-18NV - E3 MSH-12NV - E1 MSH-12NV - E2 MSH-18NV - E2 MSH-18NV MSH-24NV MSH-18NV MSH-24NV MSH-18NV - E1 - E1 - E2 - E2 - E3 MSH-07NV - E1 MSH-07NV - E2 MSH-09NV - E1 MSH-09NV - E2 MSH-12NV - E1
OB207t-1qxp 25/9/97 8:51 PM MSH-07NV - E1 Page 4 MSH-09NV - E1 REMOTE CONTROLLER 4 MSH-12NV - E1 MSH-18NV - E1 MSH-18NV - E2
OB207t-1qxp 25/9/97 8:51 PM MSH-07NV MSH-12NV MSH-07NV MSH-12NV MSH-24NV Page 5 - E1 (Serial number 7000201T~) MSH-09NV - E1 (Serial number 7000201T~) - E1 (Serial number 7000001T~) MSH-24NV - E1 - E2 MSH-09NV - E2 - E2 MSH-18NV - E2 (Serial number 7000001T~) - E2 MSH-18NV - E3 5
OB207t-1qxp 3 25/9/97 8:51 PM Page 6 SPECIFICATION Model MSH-07NV - Dehumidification K /h INDOOR 492 OUTDOOR 1620 INDOOR 492 OUTDOOR 1620 Air flow Power outlet A Running current A 3.30-3.20 3.15-3.05 4.10-4.00 4.30-4.10 W 710-750 680-720 880-920 920-940 A(kW) — — — — 98-96 97-96 Power input Auxiliary heater Electrical data % 98-98 Starting current A 25 Compressor motor current A Fan motor current A Indoor Outdoor fan motor 3.80-3.60 3.60-3.
OB207t-1qxp 25/9/97 8:51 PM Page 7 Model MSH-12NV - Power supply kW Capacity R/h Dehumidification fan motor — 2.5 5.95-6.10 9.4-9.2 9.2-9.0 10 15 W 1220-1300 1260-1350 2030-2120 1980-2070 A(kW) — — — — Power factor % 96-92 96-92 98-96 98-96 Starting current A Compressor motor current A Fan motor current A 35 5.41-5.56 5.21-5.36 52-58 8.56-8.36 8.76-8.56 INDOOR 0.17 OUTDOOR 0.37 INDOOR 0.25 OUTDOOR 0.39 2.73-2.61 2.51-2.41 3.17-2.96 2.78-2.
OB207t-1qxp 25/9/97 8:51 PM Page 8 Model MSH-24NV - Function Capacity kW 6.0 6.2 Dehumidification R/h 3.1 — Power outlet K /h 816 A 25 Running current A 12.6-11.7 Power input W 2720-2750 Power factor % 98 Starting current A 59 Compressor motor current A Fan motor current A Outdoor fan motor Output W Winding resistance(at20:) " 2200 C-R 0.96 C-S 2.07 " WHT-BLK183.8 BLK-RED250.5 " WHT-BLK62.7 BLK-YLW30.2 YLW-RED62.
OB207t-1qxp 25/9/97 8:51 PM Page 9 Refer to the Service Manual OB185 when MSH-07/09/12NVconnected with MXZ-32NV- E1 as multi system units. Model Dehumidification kW — R/h — K /h Air flow — — — — 492 10 W 35 35 A(kW) — — Power factor % 94-86 94-86 Starting current A — — Compressor motor current A — — Fan motor current A 0.17 0.
OB207t-1qxp 25/9/97 8:51 PM Page 10 Refer to the Service Manual OB185 when MSH-07/09/12NVconnected with MXZ-32NV- E1 as multi system units. Model Function Cooling fan motor K /h 558 756 — — 10 10 Running current A 0.17 0.28 W 35 60 A(kW) — — Power factor % 94-86 97-89 Starting current A — — Compressor motor current A — — Fan motor current A 0.17 0.
OB207t-1qxp 25/9/97 8:51 PM 4 Page 11 OUTLINES AND DIMENSIONS Unit: mm MSH-07NV - E1 MSH-09NV - E1 MSH-07NV - E2 MSH-09NV - E2 INDOOR UNIT MUH-07NV - E1 MUH-09NV - E1 MUH-07NV - E2 MUH-09NV - E2 OUTDOOR UNIT 11
OB207t-1qxp 25/9/97 8:51 PM Page 12 Unit: mm MSH-12NV - E1 MSH-12NV - E2 INDOOR UNIT 9.52 ides left s only / t h r rig p has nt o . o e fro nt, the t tructed h t f s I a b c o a n v are 10cm u e to b MUH-12NV - E1 MUH-12NV - E2 OUTDOOR UNIT If the right/left sides or back side is vacant,the front has only to be 50cm unobstructed.
OB207t-1qxp 25/9/97 8:51 PM Page 13 Unit: mm MSH-24NV - E1 MSH-18NV - E2 MSH-24NV - E2 4holes 11 11✕20 Indoor unit 648 217 254 60 40 20 150 995 MSH-18NV - E3 450 3 450 297 MSH-18NV - E1 INDOOR UNIT 438 352 Wall hole [75 Installation plate 1015 190 5 320 Installation plate { Air in 50 775 17.5 Air out Drain hose [16 Insulation [28 Power supply cord Lead to right 2m Lead to left 1m 160 56 190 Liquid line [8-0.5m Gas line [12-0.43m Insulation [50 O.D [28 [ 28 I.
95 For 10 units or less Rear piping hole 10 138 200 Rear fresh air intake 23 Side air intake 7 295(11-5/8) Outlet guide installation hole Handle for moving 24(1) 33 1000 524 Drain hole 441 Handle for moving 100 40 524 870(34-1/4) Drain hole 2-12✕23 Oval holes (standard bolt M10) 302 Air outlet Service panel 10 Note:Allow adequate upper clearance 10 500 Front opening 0 12 R6 Service space 65 120 60 Knock out holes for power line 2-[27 Standard bolt length MUH-24NV- E2
OB207t-1qxp 25/9/97 8:52 PM 5 Page 15 WIRING DIAGRAM MODELS WIRING DIAGRAM MSH-07NV - E1 MSH-09NV - E1 INDOOR UNIT ❈ ❈ ~ ❈ ❈ ❈ ❈ ~/N FOR MULTI SYSTEM TO OUTDOOR 12VDC UNIT CONNECTING L 3 2 N ; NAME SYMBOL SYMBOL NAME SYMBOL NAME C11 INDOOR FAN CAPACITOR NR11 VARISTOR TB TERMINAL BLOCK F12 FUSE(93:) RT11 ROOM TEMPERATURE THERMISTOR MV VANE MOTOR F11 FUSE(3.15A) RT12 INDOOR COIL THERMISTOR SR11 MF INDOOR FAN MOTOR 52C SOLID STATE RELAY CONTACTOR NOTE:1.
OB207t-1qxp 25/9/97 8:52 PM Page 16 MODEL WIRING DIAGRAM MSH-12NV - E1 INDOOR UNIT ❈ ❈ ~ ❈ ❈ ❈ ❈ ~/N FOR MULTI SYSTEM TO OUTDOOR 12VDC UNIT CONNECTING L 3 2 N ; NAME SYMBOL NAME SYMBOL NR11 VARISTOR FUSE(93:) RT11 FUSE(3.15A) RT12 C11 INDOOR FAN CAPACITOR F12 F11 MF INDOOR FAN MOTOR SYMBOL NAME TB TERMINAL BLOCK ROOM TEMPERATURE THERMISTOR MV VANE MOTOR INDOOR COIL THERMISTOR SR11 SOLID STATE RELAY CONTACTOR 52C NOTE:1.
OB207t-1qxp 25/9/97 8:52 PM Page 17 MSH-18NV - E1 MODEL WIRING DIAGRAM INDOOR UNIT ❈ ❈ ❈ ❈ ❈ ❈ NAME SYMBOL NAME SYMBOL C11 INDOOR FAN CAPACITOR NR11 VARISTOR F12 FUSE(93:) RT11 F11 FUSE(3.15A) MF INDOOR FAN MOTOR MV VANE MOTOR SYMBOL NAME TB TERMINAL BLOCK ROOM TEMPERATURE THERMISTOR DSAR SURGE ABSORBER RT12 INDOOR COIL THERMISTOR HIC1 DC/DC CONVERTER IC141 HYBRID IC 52C CONTACTOR NOTE:1.
25/9/97 8:52 PM MSH-24NV - E1 MODEL WIRING DIAGRAM 220-240V~ 3 TB❈ RED 220-240V~ 2 ❈ WHT L TO OUTDOOR BRN UNIT CONNECTING N ❈ BLU F12 HIC1 NF BLU2 3 BLU 1 4 52C ❈3 TRANS CN201 4 3 1 BLU WHT POWER SUPPLY CORD ~/N 220-240V 50Hz CN 101 3 CIRCUIT BREAKER GRN/YLW CN 151 CN 102 F11 RT12 CN 112 IC141 CN 111 NR11 INDOOR UNIT Page 18 CN 121 RT11 3 CN211 C11 OB207t-1qxp 4 2 1 BRN YLW GRY WHT RED BLK MF ELECTRONIC CONTROL P.C BOARD 5 3 MV RECEIVER DISPLAY P.C.BOARD P.C.
OB207t-1qxp 25/9/97 8:52 PM Page 19 MSH-07NV - E2 MSH-09NV - E2 MSH-12NV - E2 MODELS WIRING DIAGRAM INDOOR UNIT TO OUTDOOR TB L ❈ BRN UNIT CONNECTING BRN 12VDC 3 ❈ SR11 HIC1 RED F12 220-240V~ 2 ❈ BLU WHT BLU 1 LD101 GUARD PLATE POWER MONITOR, RECEIVER TRANS RT11 BLK 1 GRY 3 CN 121 2 3 4 WHT 5 RED 6 YLW BRN 3 2 1 CN211 ELECTRONIC CONTROL P.C BOARD C11 MF 5 MV P.C.
OB207t-1qxp 25/9/97 8:52 PM Page 20 MODEL WIRING DIAGRAM MUH-12NV - E2 OUTDOOR UNIT BLK TB N CN661 MF CN721 1 CN730 X62 SR61 ❈ WHT ❈ BLU ❈ TAB20 TRANS X62 3❈ DEICER P.C.
OB207t-1qxp 25/9/97 8:52 PM Page 21 MSH-18NV - E2 MODEL WIRING DIAGRAM INDOOR UNIT ❈ ❈ ❈ ❈ ❈ ❈ ~/N FOR MULTI SYSTEM TO OUTDOOR 12VDC UNIT CONNECTING L 3 2 N ; NAME SYMBOL NAME SYMBOL SYMBOL NAME NR11 VARISTOR FUSE(93:) RT11 ROOM TEMPERATURE THERMISTOR DSAR SURGE ABSORBER FUSE(3.15A) RT12 INDOOR COIL THERMISTOR HIC1 DC/DC CONVERTER MF INDOOR FAN MOTOR IC141 HYBRID IC MV VANE MOTOR C11 INDOOR FAN CAPACITOR F12 F11 TB TERMINAL BLOCK CONTACTOR 52C NOTE:1.
25/9/97 8:52 PM MSH-24NV - E2 Page 22 MODEL WIRING DIAGRAM TB 220-240V~ 3 ❈ RED 220-240V~ 2 ❈ WHT L TO OUTDOOR BRN UNIT CONNECTING N ❈ BLU F12 HIC1 NF BLU 2 3BLU 1 4 ❈3 52C CN201 4 3 1 BLU TRANS F11 WHT POWER SUPPLY CORD ~/N 220-240V 50Hz CN 101 3 CIRCUIT BREAKER GRN/YLW CN 151 CN 102 3 RT12 CN 112 IC141 CN 111 RT11 3 CN 121 C11 INDOOR UNIT NR11 OB207t-1qxp CN211 4 2 1 BRN YLW GRY WHT RED BLK MF ELECTRONIC CONTROL P.C BOARD 5 MV RECEIVER DISPLAY P.C.BOARD P.C.
25/9/97 8:52 PM Page 23 MSH-18NV - E3 HIC1 RED BLU WHT N❈ BLU 2 1 BLU BLU BLU BRN DSAR POWER SUPPLY CORD ~/N 220-240V 50Hz TRANS LD1 CN 151 ELECTRONIC CONTROL P.C BOARD CN CN 101 102 CN 112 RT12 3 CN 121 F11 CN211 4 2 1 BRN YLW GRY WHT RED BLK CN 111 MF RT11 5 GRN/YLW CIRCUIT BREAKER ❈ 4 ❈ 3 52C CN201 3 1 NR11 F12 220-240V~ 2 ❈ IC141 C11 TO OUTDOOR TB UNIT L ❈ BRN CONNECTING BRN 12VDC 3 ❈ GRN/YLW INDOOR UNIT MODEL WIRING DIAGRAM 3 3 MV RECEIVER DISPLAY P.C.
OB207t-1qxp 6 25/9/97 8:53 PM Page 24 REFRIGERANT SYSTEM DIAGRAM Unit:mm MSH-07NV - E1 MSH-07NV - E2 INDOOR UNIT Refrigerant pipe [ 9.52 (Option) MUH-07NV - E1 MUH-07NV - E2 OUTDOOR UNIT Muffler Reversing valve (4-way valve) (with heat insulator) Indoor heat exchanger Indoor coil thermistor RT12 Flared connection Stop valve (with service Defrost thermistor port) RT61 Strainer Room temperature thermistor RT11 Outdoor heat exchanger Capillary tube [1.
OB207t-1qxp 25/9/97 8:53 PM Page 25 Unit:mm MSH-12NV - E1 MSH-12NV - E2 INDOOR UNIT Refrigerant pipe [12.7 (Optional) (with heat insulator) Indoor heat exchanger Indoor coil thermistor RT12 Flared connection MUH-12NV - E1 MUH-12NV - E2 Reversing valve (4-way valve) OUTDOOR UNIT Muffler Stop valve (with service port) Outdoor heat exchanger Defrost thermistor RT61 RT11 Room temperature thermistor RT11 Accumulator Compressor Capillary tube [1.6x400 Flared connection Capillary tube [1.
OB207t-1qxp 25/9/97 8:53 PM Page 26 Unit:mm MSH-24NV - E1 MSH-24NV - E2 INDOOR UNIT Indoor heat exchanger Refrigerant pipe [15.88 (Option) (with heat insulator) Indoor coil thermistor RT12 Distributor MUH-24NV - E1 MUH-24NV - E2 OUTDOOR UNIT Reversing valve (4- way valve) Muffler Strainer Ball valve Outdoor heat exchanger Flared connection Room temperature thermistor RT11 Accumulator Defrost thermistor RT61 Compressor Flared connection Check valve Capillary tube [1.
OB207t-1qxp 25/9/97 8:53 PM Page 27 MAX. REFRIGERANT PIPING LENGTH Refrigerant piping Max. length : m Models A MSH-07NV - E1 MSH-09NV - E1 MSH-07NV - E2 MSH-09NV - E2 MSH-12NV MSH-12NV - E1 MSH-18NV - E1 MSH-18NV MSH-18NV - E2 MSH-24NV MSH-24NV - E1 10 Piping size O.D : mm Length of connecting pipe : m Liquid Indoor unit Outdoor unit 12.7 6.35 0.43 0 15.88 9.52 Gas 9.52 E2 15 E3 E2 MAX.
OB207t-1qxp 25/9/97 8:53 PM Page 28 EVACUATION PROCEDURES(AIR PURGE) Connect the refrigerant pipes (both the liquid and gas pipes) between the indoor and the outdoor units. Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe.
OB207t-2qxp 25/9/97 8:54 PM 7 Page 29 PERFORMANCE CURVES The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions, since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
OB207t-2qxp 25/9/97 8:54 PM Page 30 12.0 14.0 11.4 12.7 10.4 11.5 9.4 10.3 9.1 9.2 7.6 8.1 24 24 8.5 25.5 28.7 28.0 28.0 18.4 23.5 26.5 25.9 25.9 16.9 21.6 24.3 23.7 23.7 15.3 19.6 22.5 21.6 21.6 13.8 17.6 19.9 19.4 19.4 12.3 15.6 17.7 17.2 17.2 10.7 13.7 15.5 15.1 15.1 9.2 11.7 13.2 12.9 12.9 24 24 19.9 NOTE:The above curves are for the heating operation without any frost.
25/9/97 8:54 PM (kgf/F•G)(MPa•G) Outdoor low pressure 7 0.7 6 0.6 5 0.5 Page 31 MUH-09NV - E1 MUH-09NV - E1 E2 220/240V 4 0.4 3 0.3 240V Ambient temperature(˚C) Ambient humidity(%) Ambient temperature(˚C) Ambient humidity(%) 7 0.7 6 0.6 5 0.5 4 0.4 3 0.3 MUH-12NV - E1 MUH-12NV - E1 E2 Outdoor unit current (A) Outdoor low pressure (kgf/F•G)(MPa•G) 220/240V 240V Ambient temperature(˚C) Ambient humidity(%) E2 220/240V 6 MUH-18NV - E1 E3 0.6 5 0.5 4 0.4 3 0.
OB207t-2qxp 25/9/97 8:54 PM Page 32 HEAT operation Condition indoor:Dry bulb temperature 20.0°C Wet bulb temperature 14.5°C MUH-12NV - E1 E2 220V 240V Outdoor unit current (A) Outdoor unit current (A) MUH-07NV - E1 Outdoor:Dry bulb temperature 7,15,20°C Wet bulb temperature 6,12,14.
OB207t-2qxp 25/9/97 8:54 PM 8 Page 33 MICROPROCESSOR CONTROL Wireless remote controller MSH-07NV MSH-18NV MSH-07NV MSH-18NV - E1 - E1 - E2 - E2 MSH-09NV MSH-24NV MSH-09NV MSH-24NV - E1 - E1 - E2 - E2 MSH-12NV - E1 MSH-12NV - E2 MSH-18NV - E3 Once the controls are set, the same operation mode can be repeated by simply turning the OPERATE/STOP button ON. Indoor unit receives the signal with a beep tone.
OB207t-2qxp 25/9/97 8:55 PM Page 34 (4) The initial set temperature is decided by the initial room temperature.
OB207t-2qxp 25/9/97 8:55 PM Page 35 — COOL mode of “I FEEL CONTROL” — ON ON Compressor and outdoor fan motor OFF Indoor fan motor ON OFF Run continuously in cooling mode NOTE : Coil frost prevention during COOL mode of “I FEEL CONTROL” There are two types of controls in coil frost prevention. ① Temperature control When the indoor coil thermistor RT12 reads 4°C or below for 5 minutes, the coil frost prevention mode starts.
OB207t-2qxp 25/9/97 8:55 PM Page 36 Operation time chart Example ON 1st ON OFF Thermostat Indoor fan OFF ON Outdoor fan compressor ON ON ON OFF ON OFF 8 min. ON OFF 1 min. 3 min. 4 min. NOTE ● Coil frost prevention during DRY mode of “I FEEL CONTROL” The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”. However the indoor fan speed becomes the set speed or Lo. — HEAT mode of “I FEEL CONTROL” — 1.
OB207t-2qxp 25/9/97 8:55 PM Page 37 2. High pressure protection During heating operation, the outdoor fan motor is controlled by the indoor coil thermistor RT12 temperature for excess rise protection of compressor discharge pressure.
OB207t-2qxp 25/9/97 8:55 PM Page 38 (3) Defrosting time chart Defrost thermistor RT61 3.1: or more -3: or less Outdoor 52C relay(Compressor) ON OFF X62 (Reversing valve coil) ON OFF 15 sec. 30 sec. 30 sec. 5~15 sec. ON SR61 Outdoor fan OFF Defrost counter Indoor fan ON OFF ON Max 10 min. ❈ VLo OFF Indoor vane Horizontal Set position NOTE1 ● When the indoor coil thermistor reads above 18°C, indoor fan operates at VLo for 30 seconds.
OB207t-2qxp 25/9/97 8:55 PM Page 39 4. Reversing valve control Heating · · · · · ON Cooling · · · · · OFF Dry · · · · · · · · OFF NOTE1: The Reversing valve reverses for 5 seconds right before start-up of the compressor. NOTE2: Refer to the Service Manual OB185 when MSH-07/09/12NV- E1 , MSH-07/09/12/18NVare connected with MXZ-32NV- E1 as multi system units. Reversing valve ON OFF ON OFF Outdoor fan ON OFF Compressor 8-2. COOL ( (COOL / DRY) (HEAT) 5 sec. 5 sec.
OB207t-2qxp 25/9/97 8:55 PM Page 40 8-5. FAN MOTOR CONTROL (1) Rotational frequency feedback control The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feedback the rotational frequency.
OB207t-2qxp 25/9/97 8:55 PM Page 41 (3) Positioning The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle. The positioning is decided as follows. (a) When the OPERATE/STOP button is pressed. (POWER ON/OFF) (b) When the vane control is changed from AUTO to MANUAL. (c) When the SWING is finished. (d) When the test run starts. (e) When the power supply turns ON.
OB207t-2qxp 25/9/97 8:55 PM Page 42 8-8. TIMER OPERATION 1. How to set the timer (1) Press OPERATE/STOP button to start the air conditioner. (2) Check that the current time is set correctly. NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display of TIME MONITOR so set the current time, correctly with CLOCK SET button. (3) Press TIMER CONTROL button to select the operation. “ ” button... AUTO START operation (ON timer) “ ” button...
OB207t-2qxp 25/9/97 8:55 PM Page 43 8-9. EMERGENCY-TEST OPERATION When the remote controller is missing, has failed or the batteries run down, press the EMERGENCY OPERATION switch on the front of the indoor unit. The unit will start and the OPERATION INDICATOR lamp will light. The first 30 minutes of operation will be the test run operation. This operation is for servicing. The indoor fan runs at high speed and the system is in continuous operation. The thermostat is ON and the timer is reset to normal.
OB207t-2qxp 25/9/97 8:55 PM 9 Page 44 SERVICE FUNCTIONS 1. COMPULSORY DEFROSTING MODE FOR SERVICE By short circuit of the connector JP607 and R853 on the outdoor deicer P.C. board, defrosting mode can be accomplished regardless of the defrost interval restriction. See Page 56 and 59. Defrost thermistor RT61 must read below -3°C 2. DEFROST TERMINATION CHANGE when the JPC wire of the deicer P.C. board is cut, the defrost interval time will be changed. (See page 56 and 59.
OB207t-2qxp 25/9/97 8:55 PM Page 45 (2) MSH-07NV MSH-12NV MSH-07NV MSH-12NV MSH-24NV - E1 (Serial number 7000201T~) - E1 (Serial number 7000001T~) - E2 - E2 - E2 MSH-09NV MSH-24NV MSH-09NV MSH-18NV MSH-18NV - E1 (Serial number 7000201T~) - E1 - E2 - E2 (Serial number 7000001T~) - E3 How to modify the remote controller P.C. board Remove batteries before modification.
OB207t-2qxp 25/9/97 8:55 PM Page 46 5. AUTO RESTART FUNCTION MSH-07NV - E2 MSH-12NV - E2 MSH-18NV - E3 MSH-09NV - E2 MSH-24NV - E2 When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure.Then, the unit will restart automatically. However if the unit is operated in “I FEEL CONTROL.
OB207t-2qxp 25/9/97 8:55 PM 10 Page 47 TROUBLESHOOTING MSH-07NV MSH-18NV MSH-09NV MSH-24NV - E1 - E1 - E2 - E2 MSH-09NV MSH-24NV MSH-12NV MSH-18NV - E1 - E1 - E2 - E3 MSH-12NV - E1 MSH-07NV - E2 MSH-18NV - E2 10-1 Cautions on troubleshooting 10-1-1 Before troubleshooting, check the followings: 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for mis-wiring. 10-1-2 Take care the followings during servicing.
OB207t-2qxp 25/9/97 8:55 PM Page 48 10-2 Instruction of troubleshooting Start Indoor unit dosen’t receive the signal from remote controller. Indoor unit operates. Outdoor unit doesn’t operate. OPERATION INDICATOR lamp on the indoor unit is flashing on and off. 2-time flash Outdoor unit operates in only Test Run operation. Outdoor unit doesn’t operate even in Test Run operation. Refer to B ”Check of receiver P.C. board” on page 51. 2.5-second OFF 3-time flash 2.
OB207t-2qxp 25/9/97 8:55 PM Page 49 10-2-1 troubleshooting check table ❈ Before taking measures, make sure that the symptom reappears, for accurate troubleshooting. Self check table NO. Abnormal point Symptom Indication Check point Detect method 0.5-second ON Outdoor unit does not run. When serial signal stops for 4 to 5 seconds after 1st on of 52C relay by POWER turning on. ● Check wiring (visual check and conductivity check). ● Check indoor electronic control P.C.board.
OB207t-2qxp 25/9/97 8:56 PM Page 50 10-2-2 Trouble criterion of main parts MSH-07NV- E1 MSH-18NV- E1 MSH-07NV- E2 MSH-18NV- E2 MSH-09NV- E1 MSH-24NV- E1 MSH-09NV- E2 MSH-24NV- E2 MSH-12NV- E1 MSH-12NV- E2 MSH-18NV- E3 Check method and criterion Part name Room temperature thermistor Indoor coil thermistor Figure Measure the resistance with a tester. (Part temperature 10°C ~ 30°C) Normal Abnormal 8kΩ ~ 20kΩ Opened or short-circuited Measure the resistance with a tester.
OB207t-2qxp 25/9/97 8:56 PM Page 51 A Check of indoor fan motor Turn OFF power supply. Check connector CN211 visually. Inodoor fan does not operate. Yes No No Are lead wires connected? Is soldered point nomal? Yes Reconnect the lead wires. Resolder it. Disconnect lead wires from connector CN211 on indoor electronic control P.C. board. Measure resistance between lead wires No.1 and No.4 and then No.1 and No.2(MSH-18/24) No.1 and No.3 and then No.2 and No.
OB207t-2qxp 25/9/97 8:56 PM Page 52 C Check of indoor electronic control P.C. board The unit doesn’t operate with the remote controller. Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch. Replace the fuse. Trouble of indoor electronic control P.C. board. Yes Yes No Is fuse(F11)blown? Check both “parts side”and “pattern side” of indoor electronic control P.C. board visually. 1.Pull out power supply cord. 2.
OB207t-2qxp 25/9/97 8:56 PM Page 53 E How to check mis-wiring and serial signal error (when outdoor unit does not work) MSH-07NV MSH-09NV MSH-12NV MSH-18NV Start 1. Turn OFF power supply. 2. Turn ON power supply. 3. Press EMERGENCY OPERATION switch. ❈ 1 Short circuit of JPG and JPS on the indoor electronic control P.C. board enables self-check to be displayed in 3 seconds. 3 min.
OB207t-2qxp 25/9/97 8:56 PM Page 54 E How to check mis-wiring and serial signal error (when outdoor unit does not work) MSH-24NV Start 1. Turn OFF power supply. 2. Turn ON power supply. 3. Press EMERGENCY OPERATION switch. ❈ 1 Short circuit of JPG and JPS on the indoor electronic control P.C. board enables self-check to be displayed in 3 seconds. 3 min. later, what self-check result is displayed on OPERATION INDICATOR lamp on indoor unit? ❈ 1 Serial signal error is indicated. (0.5-sec.ON, 2.5-sec.
OB207t-2qxp 25/9/97 8:56 PM Page 55 TEST POINT DIAGRAM AND VOLTAGE MSH-18NV - E1 Indoor electric control P.C.board } Fan motor power supply Fuse AC250V 3.
OB207t-2qxp 25/9/97 8:56 PM Page 56 MUH-18NV - E1 Outdoor deicer P.C. board } R601 DC5~10V -- Defrost INPUT AC 220-240V thermistor(RT61) + } } Reversing valve coil AC 220-240V } } Outdoor fan motor AC 220-240V DEICER P.C. BOARD Fuse 2A/250V Defrost interval time short pin + J8 -- J7 DC12V 56 + } + } -- -- 52C DC12V Defrost termination temperature change.
OB207t-2qxp 25/9/97 8:58 PM Page 57 TEST POINT DIAGRAM AND VOLTAGE MSH-07NV - E1 MSH-09NV - E1 MSH-12NV - E1 MSH-07NV - E2 MSH-09NV - E2 MSH-12NV - E2 Indoor electronic control P.C. board } Power supply input AC 220-240V CN201 No1 Varistor(NR11) Fuse AC250V 3.15A Room temperature thermistor(RT11) Indoor coil thermistor(RT12) Time short mode point Indoor coil thermistor(RT12) Room temperature thermistor(RT11) R132 DC0~20V P.C.
OB207t-3qxp 25/9/97 9:01 PM Page 58 TEST POINT DIAGRAM AND VOLTAGE MSH-24NV - E1 MSH-18NV - E2 MSH-24NV - E2 MSH-18NV - E3 Fan motor power supply Fuse AC 250V 3.15A } + Power supply input AC 220-240V C144 } DC5V C144 Room temperature thermistor(RT11) Indoor coil thermistor(RT12) JPS Time short mode point JPS Emergency operation switch JPG + } DC12V JP41 R132 DC0~20V P.C.
MUH-12NV - E1 MUH-09NV - E2 MUH-24NV - E2 P.C. board R601 Reversing valve DC5~10V coil + AC 220-240V INPUT AC 220-240V DEICER P.C. BOARD Defrost thermistor(RT61) } } Outdoor fan motor AC 220-240V MUH-09NV - E1 MUH-07NV - E2 MUH-18NV - E2 } MUH-07NV - E1 MUH-24NV - E1 MUH-12NV - E2 MUH-18NV - E3 Outdoor deicer Page 59 } 25/9/97 9:02 PM } OB207t-3qxp Fuse 2A/250V Defrost interval time short pin + J9 J8 + } + } DC12V } DC5V 52C DC12V Defrost termination temperature change.
OB207t-3qxp 11 25/9/97 9:02 PM Page 60 DISASSEMBLY INSTRUCTIONS NOTE: ❈ On the wiring diagram shows the terminals with a lock mechanism, so it cannot be removed when you pull the lead wire Be sure to pull the wire by pushing the locking lever (projected part) of the terminal with a finger. ① Slide the sleeve. ➁ Pull the wire while pushing the locking lever. 11-1 MSH-07NV - E1 MSH-07NV - E2 INDOOR UNIT MSH-09NV - E1 MSH-09NV - E2 MSH-12NV - E1 MSH-12NV - E2 PHOTOS OPERATING PROCEDURE 1.
OB207t-3qxp 25/9/97 9:02 PM Page 61 OPERATING PROCEDURE 3. Removing the electrical box (1) (2) (3) (4) Remove the front panel. (Refer to 1) Remove the electrical cover. Disconnect the connector of the indoor coil thermistor. Disconnect the motor connector (CN211 and CN121) and the vane motor connector (CN151) on the electronic control P.C. board. (5) Unhook the catches (both upper and lower), remove the electrical box. PHOTOS Photo 3 Catch 4. Removing the vane motor (1) Remove the front panel.
OB207t-3qxp 25/9/97 9:03 PM Page 62 11-2 MSH-18NV - E1 MSH-24NV MSH-18NV - E3 INDOOR UNIT E1 MSH-18NV - E2 MSH-24NV - OPERATING PROCEDURE 1. Removing the front panel (1) Remove the screw caps at the down of the front panel. Remove the screws. (2) Pull the panel down to your side slightly and unhook the catches at the top. E2 PHOTOS Photo 1 Front panel Screws 2. Removing the electronic control P.C. board (1) (2) (3) (4) (5) (6) (7) Remove the front panel.
OB207t-3qxp 25/9/97 9:03 PM Page 63 PHOTOS OPERATING PROCEDURE 3. Removing the electrical box (1) (2) (3) (4) Remove the front panel. (Refer to 1) Remove the electrical cover. Disconnect the connector of the indoor coil thermistor. Disconnect the motor connector (CN211 and CN121) and the vane motor connector (CN151) on the electronic control P.C. board. (5) Remove the screw of the electrical box, remove the electrical box. screw Photo 3 screw 4.
OB207t-3qxp 25/9/97 9:03 PM Page 64 11-3 MUH-07NV - E1 MUH-09NV OUTDOOR UNIT E1 MUH-07NV - MUH-09NV - E2 OPERATING PROCEDURE E2 PHOTOS 1. Removing the cabinet Photo 1 (1) Remove the top panel. (2) Remove the cabinet Photo 2 Screw for top panel Screw for service panel Service panel Screw for top panel Screws for cabinet Screws for cabinet 2. Remove the deicer P.C. board (1) Remove the top panel, the service panel and the cabinet.
OB207t-3qxp 25/9/97 9:04 PM Page 65 OPERATING PROCEDURE PHOTOS 4. Removing the outdoor fan motor (1) (2) (3) (4) Remove the screws securing the outdoor fan motor. Remove the lead clamps. Disconnect the capacitor terminal and wire of the terminal. Pull out the outdoor fan motor. Photo 5 Outdoor fan motor set screws Lead fxture Outdoor fan motor 5. Removing the compressor (1) (2) (3) (4) (5) (6) (7) (8) Remove the lead clamps. Remove the screws securing the relay panel.
OB207t-3qxp 25/9/97 9:04 PM Page 66 11-4 MUH-12NV - E1 MUH-18NV MUH-18NV - E3 OUTDOOR UNIT E1 MUH-12NV - MUH-18NV - E2 OPERATING PROCEDURE E2 PHOTOS 1. Removing the cabinet (1) Remove the screws of the cabinet. (2) Hold the down of the cabinet on the both side to remove the cabinet. Photo 1 Photo 2 Screws Service panel Screws 2. Removing the deicer P.C. board (1) Remove the service panel and the cabinet. (2) Disconnect all the connectors and the terminals on the deicer P.C. board.
OB207t-3qxp 25/9/97 9:05 PM Page 67 OPERATING PROCEDURE 3. Removing the outdoor fan motor (1) Remove the cabinet. (Refer to 1) (2) Disconnect the connector remove the clamp of fan motor lead wire. (3) Remove the propeller nut and remove the propeller. (4) Remove screws securing the fan motor. PHOTOS Photo 4 propeller fan Set screws for outdoor fan motor Lead clamps Outdoor fan motor Propeller fan nut Set screws for outdoor fan motor 4. Removing the compressor (1) (2) (3) (4) Remove the cabinet.
OB207t-3qxp 25/9/97 9:05 PM Page 68 11-5 MUH-24NV- E1 MUH-24NV- E2 OUTDOOR UNIT OPERATING PROCEDURE 1. Removing the electrical parts (1) Remove the screws and the top panel. (2) Remove the screw of the cover panel. To remove the cover panel, pull it toward you and unhook the catches from the side panel. (3) Remove the screw of the service panel. To remove the service panel, pull it down toward you and unhook the catches on the both sides.
OB207t-3qxp 25/9/97 9:05 PM Page 69 OPERATING PROCEDURE 3. Removing the heat exchanger and the compressor (1) Remove the rear panel.Remove the valve bed, and open the rear panel to the rear to remove. NOTE : All panels are fixed by catches, and must be removed by shifting up and down. (2) Remove the screws of the right side panel and remove it. (3) Remove the screws of the rear guard and remove it. (4) Remove the screws of the separator support plate and remove it.
OB207t-3qxp 12 25/9/97 9:06 PM Page 70 PARTS LIST INDOOR UNIT STRUCTURAL PARTS MSH-07NV - E1 (WH) MSH-09NV - E1 (WH) MSH-12NV - E1 (WH) MSH-07NV - E2 (WH) MSH-09NV - E2 (WH) MSH-12NV - E2 (WH) 5 1 6 4 2 Optional parts 3 Symbol NO. Part No.
OB207t-3qxp 25/9/97 9:07 PM Page 71 INDOOR UNIT ELECTRICAL PARTS MSH-07NV - E1 (WH) MSH-09NV - E1 (WH) MSH-12NV - E1 (WH) MSH-07NV - E2 (WH) MSH-09NV - E2 (WH) MSH-12NV - E2 (WH) 10 9 7 8 16 6 3 5 1 2 4 13 12 Part number that are circled is not shown in the illustration. NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Part No.
OB207t-3qxp 25/9/97 9:07 PM Page 72 OUTDOOR UNIT STRUCTURAL PARTS MUH-07NV - E1 MUH-09NV - E1 MUH-07NV - E2 MUH-09NV - E2 5 13 11 2 1 9 10 7 8 4 3 6 Part number that are circled is not shown in the illustration. Symbol NO. Part No.
OB207t-3qxp 25/9/97 9:07 PM Page 73 OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS MUH-07NV - E1 MUH-09NV - E1 MUH-07NV - E2 MUH-09NV - E2 6 5 1 2 4 3 Part number that are circled is not shown in the illustration. Symbol NO. Part No.
OB207t-3qxp 25/9/97 9:08 PM Page 74 OUTDOOR UNIT STRUCTURAL PARTS MUH-12NV - E1 MUH-12NV - E2 3 17 18 15 16 2 14 7 12 4 10 11 13 6 5 8 9 1 Part number that are circled is not shown in the illustration. Symbol NO. Part No.
OB207t-3qxp 25/9/97 9:09 PM Page 75 INDOOR UNIT STRUCTURAL PARTS MSH-18NV - E1 (WH) MSH-24NV - E1 (WH) MSH-18NV - E2 (WH) MSH-24NV - E2 (WH) MSH-18NV - E3 (WH) 1 5 3 2 Optional parts 6 4 Part number that are circled is not shown in the illustration. Symbol NO. Part No.
OB207t-3qxp 25/9/97 9:09 PM Page 76 INDOOR UNIT ELECTRICAL PARTS MSH-18NV - E1 (WH) MSH-24NV - E1 (WH) MSH-18NV - E2 (WH) MSH-24NV - E2 (WH) MSH-18NV - E3 (WH) 10 8 11 15 5 5 7 4 3 16 1 9 6 12 2 14 17 Part number that are circled is not shown in the illustration. Symbol NO. Part No.
OB207t-3qxp 25/9/97 9:10 PM Page 77 OUTDOOR UNIT STRUCTURAL PARTS MUH-18NV - E1 MUH-18NV - E2 MUH-18NV - E3 17 20 19 12 8 10 4 1 22 15 16 9 2 5 3 7 14 6 Part number that are circled is not shown in the illustration. Symbol NO. Part No.
OB207t-3qxp 25/9/97 9:11 PM Page 78 OUTDOOR UNIT STRUCTURAL PARTS MUH-24NV- E1 MUH-24NV- E2 17 13 22 1 2 7 5 3 19 10 18 11 24 23 8 4 20 9 12 78 14 6 15 16
OB207t-3qxp 25/9/97 9:11 PM Page 79 OUTDOOR UNIT STRUCTURAL PARTS MUH-24NV- E1 MUH-24NV- E2 Part number that are circled is not shown in the illustration. Symbol NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Part No.
OB207t-3qxp 25/9/97 9:11 PM 13 Page 80 OPTIONAL PARTS 1. REFRIGERANT PIPES The air conditioner has flared connections its indoor and outdoor sides. Please use the optional extension pipe as follows. Model MSH-07NVMSH-09NVMSH-07NVMSH-09NV- E1 MSH-12NVMSH-12NV- E1 MSH-18NVMSH-18NVMSH-18NV- E1 MSH-24NVMSH-24NV- E1 E2 E2 E2 E2 E3 E1 E2 Part No.