Unit installation

Specifications
18
17
System Controls
System Controls
(
SUZ and Mr. Slim Power Inverter only
)
Versatile system controls can be realised by using optional parts, relay circuits, control panels, etc.
Single-remote controller
control
Standard system
Dual Remote Controllers
Two remote controllers, one each
for local and remote control of the
system
Group control
One remote controller can control
multiple air conditioners simulta-
neously using the same setting.
* The setting of the refrigerant
address is required for outdoor unit.
Operation Control by
level signal
(
12VDC
)
Turn on/off unit from a remote
location, prohibit/permit
operation using a local remote
controller
Operation control by
pulse signal
Remote display of
operating status
Operating status can be
displayed at a remote location.
On/Off timer enabled
* For the control by external timer,
refer to D operation control by
level signal.
Centralised control of
dispersed air conditioning
equipment allows effective
monitoring/controlling.
Lossnay can be controlled with
a remote controller.
Timer Operation
Centralised control
(for Power Inverter only)
Interlocking with
Lossnay
PAR-21MA A
(
Example of 1 : 1 system
)
(
Example of 1 : 1 system
)
(
Example of 1 : 1 system
)
Relay box (to be purchased locally)
(
Example of 1 : 1 system
)
PAR-21MA A
Lossnay operation cable
Lossnay
Wired remote
controller
(
Connection with M-NET system
)
Centralised remote
controller G-50, etc.
Power supply unit
M-NET adapter
PAC-SF80MA-E
PAR-21MA A
(
Example of 1 : 1 system
)
* Set “Main” and “Sub”
remote controllers.
• Wired remote controller
PAR-21MAA
• Wired remote controller kit for PKA
PAR-21MAAT-E
• Wireless remote controller
PAR-SL97A-E
• Wireless remote controller kit for PCA
PAR-SL99B-E
MAC-397 IF-E is required for each
indoor unit if the outdoor unit is SUZ
or MXZ
(
if the outdoor unit is P Series,
no optional parts are required
)
• Adapter for remote On/Off
PAC-SE55RA-E
• Relay box
(to be purchased locally)
• Remote control panel
(to be purchased locally)
Standard functions of PAR-21MAA
PAC-SF81MA-E
Slim-Lossnay connection cable
A
B
C
D
E
F
G
H
I
Details Major optional parts required
System examples
Wired remote controller
Wireless remote controller
Remote
display
panel
PAR-21
MAA
Relay box (to be purchased locally)
Adapter for
remote
On/Off
Adapter for
remote
On/Off
PA R- SL97A- E
(
Example of 1 : 1 system×2
)
Relay box (to be purchased locally)
(
Example of 1 : 1 system×2
)
Remote
control
panel
Remote
control
panelWired remote
controller
• Either wired or wireless remote
controller can be used
• Up to two remote controllers can
be connected to one group
• Both wired and wireless remote
controllers can be used in
combination
• One remote controller can control
up to 16 refrigerant systems
• Outdoor unit can be started/
stopped
(
thermostat On/Off
)
individually.
• Up to two remote controllers can
be connected
• Operation other than On/Off
(adjustment of temperature, fan
speed, and air direction, for
example) can be performed even
when remote controller operation
is prohibited
• Timer control is possible with
an external timer
Connector
cable for
remote
display
Connector
cable for
remote
display
PA R- SL97A- E
(
Example of 1 : 1 system×2
)
Relay box (to be purchased locally)
(
Example of 1 : 1 system×2
)
• Connector cable for remote display
PAC-SA88HA-E/PAC-725AD
(
10 pcs. × PAC-SA88HA-E
)
• Relay box
(to be purchased locally)
Remote control panel
(to be purchased locally)
Remote
control
panel
Remote
control
panelWired remote
controller
• The pulse signal can be turned
On/Off.
• Operation/Fault signal can be
received at a remote location
(
12VDC signal
)
Weekly Timer:
On/Off and up to eight pattern
temperatures can be set for each
calendar day (initial setting)
Simple Timer:
Unit can be set to turn on/off one
time each in a 72hr period; setting
intervals of 1hr
Auto-off Timer:
Unit turns on/off after a specified
time elapses. Can be set in the range
from 30min to 4hr at intervals of 30min.
*Simple Timer and Auto-off Timer cannot be
used at the same time.
• Mounting the adapter for M-NET
connection to the outdoor unit
allows MELANS
(
M-NET system
)
connection
• Allows centralised control by
MELANS
• Lossnay can be connected to
the indoor unit
None
• Remote display panel
(to be purchased locally)
• Connector cable for remote display
PAC-SA88HA-E/PAC-725AD
(
10 pcs. × PAC-SA88HA-E
)
• Relay box (to be purchased locally)
• Remote operation adapter
PAC-SF40RM
* Cannot be used with wireless remote controller
• Remote display panel
(to be purchased locally)
PAR-21MA A
(
Example of 1 : 1 system×2
)
MAC-397IF-E*
Remote operation adapter/
Connector cable for remote display +
relay box
MAC-397IF-E
(
Interface
)
MAC-821SC-E
(
Centralised remote controller
)
• Centralised remote controller can be
connected to each indoor unit via
interface.
Units can be turned on/off
independently or simultaneously
using a centralised controller
On/Off statues of each unit can be
confirmed viewing the LED display of
the centralised controller
Centralised On/Off control
(for All Outdoor Units)
Up to eight indoor units can be
switched On/Off with one
remote controller.
Indoor unit
MAC-821SC-E
MAC-397IF-E
Outdoor unit
• Operation/Fault signal can be
received at a remote location
(when channeled through the
PAC-SF40RM no-voltage signal,
when channeled through the
PAC-SA88HA-E 12VDC signal
)
*Above specifications are for outdoor units only.
SUZ-KA25VA2 SUZ-KA35VA 2 SUZ-K A50VA2 SUZ-KA60VA 2 SUZ-K A71VA2
Specifications: Outdoor Unit
Outdoor unit
Power supply
Compressor output
Airflow (cooling/heating)
Cooling mode
Heating mode
Height
Width
Depth
Sound pressure
level
(
dB
)
Sound level
Dimensions
Weight
Chargeless piping length
Max. piping length
Breaker size
(mm)
(mm)
(mm)
(
kW
)
CMM
(
L /S
)
(
dB
)
(
kg
)
(m)
(m)
(
A
)
*Above specifications are for outdoor units only.
PUHZ-RP71VHA3 PUHZ-RP100V/YHA2 PUHZ-RP125V/YHA2 PUHZ-RP140V/YHA2
Munsell 3.0Y 7.8/1.1
V: Single-phase, 50Hz, 230V Y: Three-phase, 50Hz, 400V
1.6 1.9 2.4 2.9
55
(
920
)
49
100
(
1670
)
47
46
50 50
44
51
47 48
48
69
52 52
7166 70
943 1350
950 950
330+30 330+30
75 121 116
30 30
50 75
Discharge thermo, HP switch Discharge thermo, HP switch
8.0 4 / 9.74 V: 12.53/12.39 Y: 4.08/4.03 V: 15.53/15.98 Y: 5.04/5.20 V: 19.65/19.92 Y: 6.37/6.46
25 V: 32 Y: 16 V: 32 Y: 16 V: 40 Y: 16
Outdoor unit
Power supply
Compressor output
Airflow (cooling/heating)
Cooling mode
Heating mode
Height
Width
Depth
Sound pressure
level
(
dB
)
Sound level
Dimensions
Weight
Chargeless piping length
Max. piping length
Protection device
(mm)
(mm)
(mm)
(
kW
)
CMM
(
L /S
)
(
dB
)
(
kg
)
(m)
(m)
Silent mode
Rated running current
(cooling/heating)
(
A
)
Breaker size
(
A
)
External finish
External finish Munsell 3.0Y 7.8/1.1
Single-phase, 50Hz, 230V
0.55 0.65 0.85 1.2
34 (568)/32 (534) 33 ( 551) 49 (818) 50 (835)/48 (800)
46 47 53 55
46 48 55 55
59 61 68 69
550 850 880
800 840 840
285 330 330
33 37 53 53
7
20 30
10 20