Unit installation
PCA
SERIESSERIES
PKA
SERIESSERIES
13
Ceiling-suspended
14
Wall-mounted
A stylish indoor unit design and airflow
settings for both high- and low-ceiling
interiors expand installation possibilities
Stylish Indoor Unit Design
A stylish square-like design is adopted for
the indoor units of all models. As a result,
the units blend in better with the ceiling.
PCA-GA
PCA-KA
Optional Drain Pump for
Full-capacity Models
The pumping height of the optional drain
pump has been increased from 400mm
to 600mm, expanding flexibility in choos-
ing unit location during installation work.
Drainage outlet can
be 600mm above
ceiling surface
Drain pump installation
possible
Ceiling
surface
Auto-flap Shutter Enhances Good Looks
The Intake Grille Filter Can be Completely
Removed Allowing Easy Cleaning
(Can be washed in water)
Filter slides out
4-way Piping Provides More Flexibility
in Selecting Installation Sites
Wired Remote Controller Available
(Option)
A separately sold wired remote controller and a terminal block
are available to suit various installation sites.
Drain Pump Option Available with
All Models
Installation of the drain pump enables a drain outlet as high as
800mm above the base of the indoor unit. Drain water can be
discharged easily even if the surface where the wall-mounted
unit does not have direct access outside, increasing the degree
of freedom for installation.
Elegant design and compact dimensions
are ideal for offices, stores and
residential-use
Equipped with Automatic Air-speed Adjustment
In addition to the conventional 4-speed setting, units are now
equipped with an automatic air-speed adjustment mode. This set-
ting automatically adjusts the air-speed to conditions that match
the room environment. At the start of heating/cooling operation,
the airflow is set to high-speed to quickly heat/cool the room.
When the room temperature reaches the desired setting, the
airflow speed is de-
creased automatical-
ly for stable comfort-
able heating/cooling
operation.
Start of
cooling/heating…
After room
temperature is stabilised…
Strong Gentle
Fresh Outside-air Intake
Units are equipped with a knock-
out hole that enables the induc-
tion of fresh outside-air.
Airflow volume (m
3
/min)
50
0
–50
–100
–150
–200
–250
–300
0 1 2 3 4
Static pressure (Pa)
●
Outside-air intake characteristics
RP100–140
PCA-RP60/71KA
PCA-RP50KA
Capacity
High
ceiling
Standard
ceiling
Low
ceiling
50
60
71
100
125
140
3.5m
3.5m
3.5m
4.2m
4.2m
4.2m
2.7m
2.7m
2.7m
3.0m
3.0m
3.0m
2.5m
2.5m
2.5m
2.6m
2.6m
2.6m
Equipped with High- /Low-ceiling Modes
Units are equipped with high-
and low-ceiling operation modes
that make it possible to switch
the airflow volume to match room
height. The ability to choose the
optimum airflow volume makes it
possible to optimise the breezy
sensation felt throughout the room.
PKA-RP71/100FAL
PCA-RP50/60/71/100/125/140KA
800mm
Drain pump
Indoor unit
Indoor unit
Specifications: Ceiling-suspended
(
PCA
)
PCA-RP50KA
PCA-RP50KA
SUZ-KA50VA2
Cooling Heating
PCA-RP60KA
PCA-RP60KA
SU Z-K A6 0VA 2
Cooling Heating
PCA-RP71K A
PCA-RP71K A
167-183-217-250 250-267-283-317 267-283-300-333
32-34-37-40
960
25
33-35-37-40
1,280
35-37-39-41
SU Z-K A71VA 2
Cooling Heating
5.0 (1.1-5.6) 5.5 (0.9-6.6) 5 .7 ( 1.1- 6.3 ) 6.9 (0.9-8.0) 7.1 ( 0. 9 -8.1) 7.9 (0.9-10.2)
1.66 1.71 1.77 2.02 2.06 1.96
3.01 3.22 3.22 3.42 3.45 4.03
PCA-RP71K A
PCA-RP71K A
PUHZ-RP71VHA3
Cooling Heating
PCA-RP100K A
PCA-RP100K A
PUHZ-RP100V/YHA2
Cooling Heating
PCA-RP125K A
PCA-RP125K A
PUHZ-RP125V/YHA2
Cooling Heating
PCA-RP140KA
PCA-RP140KA
PUHZ-RP140V/YHA2
Cooling Heating
10.0 (4.9-11.4) 11.2 (4.5-14.0) 12.5 (5.5-14.0) 14.0 (5.0-16.0) 14.0 (5.5-15.3) 16.0 (5.0-18.0)
2.62 3.02 3.88 3.88 4.65 4.43
3.81 3.71
7.1 ( 3 .3 - 8.1 ) 8.0 (3.5 -10. 2)
1.97 2.22
3.61 3.61 3.22 3.61 3.01 3.61
V: Single-phase, 50Hz, 230V Y: Three-phase, 50Hz, 400V
367-400-433-467 383-417-450-483 400-433-483-533
37-39-41-43 39-41-43-45 41-43-45-48
230
1,600
680
36
10 -11-13-15 15-16 -17-19 16 -17-18-20 22-24-26-28 23-25-27-29 24-26-29-32
32 38 39
Outdoor unit
Function
Capacity (min.-max.)
Input
Rated EER/COP
Indoor unit
Power supply
Airflow
(
Lo-Mi2-Mid-Hi
)
Sound pressure level
Dimensions Width
Depth
Height
(
kW
)
(
kW
)
L/S
CMM
(
dB
)
(
kg
)
(mm)
(mm)
(mm)
Weight
Indoor unit
Specifications: Wall-mounted
(
PKA
)
PK A-RP71FAL
PK A-RP71FAL
PUHZ-RP71VHA3
Cooling Heating
PK A-RP10 0FAL
PK A-RP10 0FAL
V: Single-phase, 50Hz, 230V Y: Three-phase, 50Hz, 400V
22-28
367-467
41-46
340
1,680
235
28
15-20
250-333
39-45
1,4 00
24
PUHZ-RP100V/YHA2
Cooling Heating
10.0 (4.9-11.4) 11.2 (4.5-14.0)
2.93 3.25
3.41 3.45
7.1 ( 3 .3 - 8.1 ) 8.0 (3.5 -10. 2)
1.98 2.40
3.59 3.33
Outdoor unit
Function
Capacity (min.-max.)
Input
Rated EER/COP
Indoor unit
Power supply
Airflow
(
Lo-Hi
)
Sound pressure level
Dimensions Width
Depth
Height
(
kW
)
(
kW
)
L/S
(
dB
)
(
kg
)
(mm)
(mm)
(mm)
Weight
CMM
optional