Specifications

36
PCA COOLING-ONLY
LIMITED WARRANTY Seven-year warranty on compressor. Five-year warranty on parts.
Model Name
Indoor Unit PCA-A24KA PCA-A30KA PCA-A36KA PCA-A42KA
Outdoor Unit PUY-A24NHA3 (-BS) PUY-A30NHA3 (-BS) PUY-A36NHA3 (-BS) PUY-A42NHA3 (-BS)
Cooling *1
Rated Capacity Btu/h 24,000 30,000 35,000 42,000
Capacity Range Btu/h 12,000-24,000 12,000-30,000 12,000-35,000 18,000-42,000
Total Input W 2,340 3,760 4,630 4,110
Energy Efficiency SEER 16.8 14.5 14.4 15.8
Moisture Removal Pints/h 5.8 8.3 8.5 11.7
Sensible Heat Factor 0.73 0.69 0.73 0.69
Power Supply Phase, Cycle, Voltage 1-phase, 60Hz, 208 / 230V *2
Voltage
Indoor - Outdoor S1 - S2 AC 208 / 230V
Indoor - Outdoor S2 - S3 DC24V
Indoor - Remote Controller DC12V: Wired Type
Indoor Unit
MCA A 1 2
Fan Motor F.L.A. 0.54 0.97
Fan Motor Output W 95 160
Airflow (Lo-M1-M2-Hi)
DRY (CFM) 530-565-600-670 565-600-635-705 775-850-920-990 810-885-955-1,025
WET (CFM) 495-530-565-635 530-565-600-670 705-775-850-920 740-810-885-955
Sound Pressure Level (Lo-M1-M2-Hi) dB(A) 33-35-37-40 35-37-39-41 37-39-41-43 39-41-43-45
External Finish Color Munsell No. 6.4Y 8.9 / 0.4
Dimension Unit
W: In. 50-3/8 63
D: In. 26-3/4
H: In. 9-1/16
Weight Unit Lbs. 71 79 84
Field Drainpipe Size O.D. In. 1-1/16
Outdoor Unit
MCA A 18 25 26
MOCP A 30 40
Fan Motor F.L.A. 0.75 0.4 + 0.4
Fan Motor Output W 75 86 + 86
Compressor
Model (Type) DC INVERTER-driven Twin Rotary INVERTER-driven Scroll
R.L.A. 12 20
L.R.A. 14 17.5 27.5
Airflow CFM 1,940 3,530
Refrigerant Control Linear Expansion Valve
Sound Pressure Level at Cooling *1 dB(A) 48 51
External Finish Color Munsell No. 3Y 7.8 / 1.1
Dimensions
W: In. 37-3/8
D: In. 13 + 1-3/16
H: In. 37-1/8 53-1/8
Weight Lbs. 163 258
Remote Controller Type Wired Remote Controller (Packaged with Indoor Unit)
Refrigerant
Type R410A
Charge Lbs. 6, 10 10
Oil Type (fl. oz.) FV50S (28) FV50S (45)
Refrigerant Pipe
Gas Side O.D. In. 5/8
Liquid Side O.D. In. 3/8
Refrigerant Pipe Length
Height Difference (Max.) Ft. 100
Length (Max.) Ft. 165
Connection Method Indoor/Outdoor Flared/Flared
NOTES: Test conditions are based on AHRI 210/240.
*1 Rating conditions (cooling)-Indoor: D.B. 80º F (27º C), W.B. 67º F (19º C); Outdoor: D.B. 95º F (35º C), W.B. 75º F (24º C).
*2 Indoor units receive power from outdoor units through field-supplied interconnected wiring.
Specifications are subject to change without notice.
BS = Seacoast Protection
(PCA-A36KA MODEL SHOWN)