Unit installation

August 2012 Application Note 1024
©2012 Mitsubishi Electric US, Inc.
P a g e | 3
Supplemental Heat Control via CN-24 for PLA, PCA and SLZ Indoor Units
CN-24 controls are indicated in Figure 1and require no setup at the remote controller.
This function is only available in heating operation.
Figure 1. CN-24 controls
Figure 2 illustrates a typical wiring diagram for PLA, PCA and SLZ indoor units using
CN-24:
Figure 2. Wiring Diagram for PLA, PCA and SLZ Indoor Units using CN-24
Supplemental Heat Control via CN-24 for PEA (D) and SEZ Indoor Units
CN-24 controls are indicated in Figure 1 and require no setup at the remote controller.
This function is only available in heating operation. This default operation is highly
recommended.
If desired, the dead-band to energize supplemental heat can be tightened to 1.8° F via
remote controller settings. Note: This setting will result in the supplemental heat always
being energized any time the indoor unit is actively heating. Via the MHK1 Wireless
Remote Controller, enter the Installer Setup Menu and select Setup Function 123 and
select setting #2; From the PAR-21MAAU Wired Remote Controller select mode 23 and
select setting #2. (Controller manuals currently do not label this action for this function).
Due to continuing improvement, above specification may be subject to change without notice.