Unit installation

July 2009 Application Note 1023
©2012 Mitsubishi Electric US, Inc.
P a g e | 2
Figure 1: R410A P-Series Indoor Fan Cycle Off in Heat or Cool Mode with PAR-21MAA
Controller
Here are the 5 Steps to setting up the PAR-21MAA Controller displayed in Figure 1:
1. Press the airflow up/down (J) button and test (B) button at the same time for two
seconds
2. Wait for a few seconds until the small dashes start to flash then press the clock
(C) buttons to change refrigerant address to 00 then press the clock on/off (D)
button then the clock (C) buttons to change unit number to 01
3. Press the back (E) button then wait for a few seconds until the big dashes start to
flash then press the temperature up/down (F) button to change mode number to
25 for heating then the menu (G) button then the temperature up/down (F) button
to change the setting number to 2 then press the back (E) button until the
number stop flashing now it is set
4. Press the back (E) button then wait for a few seconds until the big dashes start to
flash then press the temperature up/down (F) button to change mode number to
27 for cooling then the menu (G) button then the temperature up/down (F) button
to change the setting number to 2 then press the back (E) button until the
number stop flashing now it is set
5. Press the airflow up/down (J) button and test (B) button at the same time for two
seconds to get back to normal display
Note: Use of the PAR-21MAA controller with M-series units for fan cycling is not
applicable.
Due to continuing improvement, above specification may be subject to change without notice.