MEMO: Refrigerant Accessories
Please be advised that we do not recommend the following accessories on our ductless
air conditioners or heat pump units.
Filter Driers: Our units are made in the factory under clean conditions and are brazed
using dry nitrogen. They are charged with clean oil and new refrigerant. When the line
sets are attached using flare connections the copper is clean. Under clean conditions
filter driers are not necessary and will only cause pressure drops in the system.
Sight Glasses: The outdoor unit contains the metering device. The purpose of a sight
glass is to check the condition of the liquid refrigerant prior to metering device. Since
sight glasses are placed prior to the metering device at the indoor the sight glass would
be useless and only create a pressure drop in the lines.
Traps: Traps create pressure drops in our systems. They are commonly used to help in
oil return to the compressor. Since the velocity of the refrigerant is greater when the
metering device is placed in the outdoor unit oil return is not a problem. If a trap is not
preventable, it must be a minimum of twelve inches in length.
Albert R. Blyler
Senior Application Specialist
Mitsubishi HVAC