Unit installation
July 2008 Application Note 1003
©2012 Mitsubishi Electric US, Inc.
P a g e | 2
1. All MSY/MSZ indoor units must be powered from the outdoor unit.
(Indoor unit cannot be powered from a separate source)
2. Outdoor unit power is 208/230 VAC using a two-conductor wire with ground.
3. Indoor unit power is supplied from the outdoor unit from a terminal block marked S1, S2, S3.
4. Connect the indoor unit to the outdoor unit on terminals S1, S2, S3 and ground. Use copper
conductors only.
5. A three-pole disconnect switch may be used for shut off or service between the indoor and
outdoor unit as shown in Figure 1.
Figure 1. 3 pole switch part # TAZ-MS303
Note: All wiring shall comply with NEC and local electrical codes.
Refer to unit installation manual for more details.
CONNECTING WIRES AND CONNECTING GROUND WIRE
Use a solid conductor or stranded conductor AWG14.
Use doubled insulated copper wire with 300 volt
insulation.
Use copper conductors only.
Follow national and local electrical code.
POWER SUPPLY CABLE AND GROUND WIRE
Use solid or stranded conductor AWG12** or AWG14
wire.
Use copper conductors only.
Follow national and local electrical code.
Due to continuing improvement, above specification may be subject to change without notice.