Unit installation

May 2009 Application Note 1016
©2012 Mitsubishi Electric US, Inc.
P a g e | 3
is to be used for each indoor unit with connected outdoor unit. The MAC-399IF can only
be used with the inverter models of the M-Series (MXZ/MSY/MSZ).
Note: The MAC-399IF M-NET converter cannot be used together with the MAC-397IF hard wire MA
controller adapter on the same unit. If connection to the Centralized Controller and a hard wired remote
controller is needed, use the ME controller for connection to the M-NET.
The Mr. Slim® M-Series can receive an external Enable/Disable signal by Breaking S1,
S2, and S3 at the indoor unit. Breaking these terminals will allow an automation system
the ability to schedule the Mr. Slim M-Series units On/Off.
Applications
P-Series
When the P-Series units are to be integrated into the CITY MULTI® network with the
Centralized Controllers the following components are needed:
PAC-SF81MA M-NET converter (per outdoor unit)
AG-150/GB-50/GB-24 Centralized Controller
When the P-Series units are to be integrated into the CITY MULTI® network with TG-
2000 the following components are needed:
PAC-SF81MA M-NET converter (per outdoor unit)
AG-150/GB-50 Centralized Controller
TG-2000 software
Dedicated PC Runs TG-2000 software
SW-Mon/SW-Sch Monitoring and Scheduling software (minimum software
required) for each connected Centralized Controller
SW-Charge Tenant Billing software for each connected Centralized Controller
(optional)
When the P-Series units are to be integrated into LonWorks® network the following
components are needed:
PAC-SF81MA - M-NET converter (per outdoor unit)
AG-150/GB-50 Centralized Controller (recommended)
LMAP03U LonWorks® Interface
When the P-Series units are to be integrated into the BACnet® network the following
components are needed:
PAC-SF81MA M-NET converter (per outdoor unit)
AG-150/GB-50 Centralized Controller
SW-BACnet (PAC-YTG31CDA) needed for each connected Centralized
Controller
BACnetIF software located on the CITY MULTI Controls Network CD
(CMCN CD)
Dedicated PC PC runs BACnetIF software, must have 2 LAN cards, handles up
to 10 Centralized Controllers
Due to continuing improvement, above specification may be subject to change without notice.
2013 P-Series and M-Series - Application Notes (June 2013)
APP-39