Unit installation
August 2009 Application Note 1006
©2012 Mitsubishi Electric US, Inc.
P a g e | 2
1. Only 24,000 and 36,000 BTU units can be twinned.
2. The two indoor units must equal the capacity of the outdoor unit when added
together.
3. Indoor units must be in the same conditioned space since the two return air
temperature sensors will be averaged for the space temperature control.
4. The indoor units must be powered from the outdoor unit in a daisy chain fashion as
shown in Figure 1.
Note: * A disconnect switch (part# TAZ-MS303) may be required by local code at
the indoor unit.
** Use a ring tongue terminal to connect ground wire and AWG 12 wire to
terminals.
Figure 1. Simultaneous Twin Operation
A= Outdoor unit power supply
B=Wiring circuit breaker or isolating switch
C= Outdoor unit
D= Indoor unit/Outdoor unit connecting wiring
E= Remote Control
F= Indoor unit
Note: All wiring shall comply with NEC and local electrical codes.
Refer to installation manual for more details.
CONNECTING WIRES AND CONNECTING GROUND WIRE
Use a solid conductor or stranded conductor AWG14-3.
Use doubled insulated copper wire with 600 volt insulation.
Use copper conductors only.
Follow national and local electrical code.
POWER SUPPLY CABLE AND GROUND WIRE
Use solid or stranded conductor AWG12** or AWG14 wire.
Use solid or stranded conductor AWG14 wire only on S3 communication terminal.
Use copper conductors only.
Follow national and local electrical code.