Unit installation

July 2008 Application Note 1005
©2012 Mitsubishi Electric US, Inc.
P a g e | 2
1. All MSZ indoor units must be powered from the outdoor unit.
(Indoor unit cannot be powered from a separate source).
2. MXZ outdoor unit power is 208/230 VAC circuit using a two-conductor wire with
ground.
3. Each indoor unit is powered from the outdoor unit from a terminal blocked marked to
the specific indoor unit.
4. Connect the indoor unit to the outdoor unit on terminals S1, S2, S3 and ground. Use
copper conductors only.
5. A three-pole disconnect switch may be used for shut off or service between the indoor
and outdoor unit. (3 pole switch part # TAZ-MS303)
Remark: *A disconnect switch may be required at the indoor unit. Check the local
code.
** Use a ring tongue terminal in order to connect a ground or AWG 12 wire to
terminal block.
Figure 1. 3 pole switch part # TAZ-MS303
Due to continuing improvement, above specification may be subject to change without notice.
2013 P-Series and M-Series - Application Notes (June 2013)
APP-12